Moeller Marine XI/OC SIGNAL MODULES 05/02 AWB2725-1452GB User Manual

Page of 38
Technical data
05/02 AWB2725-1452GB
26
Relay output module
Type
XIOC-12DO-R
Output type
Relay output
Output voltage
100/240 V AC, 24 V DC
Switching current, minimum
1 mA
Maximum load current
Per circuit
2A
Per common potential terminal
5 A
Output signal delay
OFFl ON 
F 10 ms 
ON l OFF
F 10 ms 
Number of output channels
12 channels/module
Number of channels with common reference potential
12 channels per reference potential
1)
Overvoltage protection
External
Fuse
External
Electrical isolation
Through optocouplers
Output indication
By LED (green)
External connection
Plug-in terminal block
Internal current consumption (5 V DC)
Typ. 40 mA
External applied voltage
2)
 
(for relay operation) 
24 V DC (+20 %, –15 %) 
(max. 70 mA)
Weight
0.2 kg
1) The reference potential terminals are internally connected.
2) An external 24 V DC voltage must applied. 
Figure 31:
Terminal assignment for the XIOC-12DO-R module
+24 V 
H
0 V 
H
+24 V 
H , 100/240 V h
0 V, N
0
1
2
3
4
5
C
24 V 
H
6
7
8
9
10
11
C
0 V