5.4  Input Calibration Set Up and Wiring 
5.4.1  General Calibration Set Up 
DIP switch settings 
Before starting the calibration activity, check that the input switches SW6 on the applicable printed circuit 
assembly (pen 1 or pen 2) are set correctly for the type of sensor being calibrated. (See Section 4 – 
Configuration, Startup, and Operation of Recorder With Display.
)  
 
General set up procedure 
Table 5-4 lists the general set up procedure for all methods of calibration. Do this procedure and then refer 
to the set up procedure and diagram specific to your input type. 
 
Table 5-4  General Calibration Set Up Procedure 
Step Action 
Set up and connect the calibrator to the input terminals for the applicable printed circuit 
assembly in your recorder according to the type of input sensor being used. Refer to the 
following figures for corresponding set-up diagrams: 
Route leads (for example: copper leads or thermocouple extension wires) through a conduit 
hole in the recorder case so that you will be able to close the chart plate. 
Close the chart plate after you have completed the applicable calibration set up.