DR4300 Circular Chart Recorder Product Manual 
12/03 
Millivolts, Volts and Milliamps inputs  
 
Table 5-8  Set Up Wiring Procedure for Calibrating Millivolts, Volts, and Milliamps Inputs 
Step Action 
Connect the copper wire to the calibration source (see Figure 5-5). 
Connect the other end of the copper wire to the TB2 terminals on the printed circuit assembly 
for the input channel being calibrated. 
 
Main PCA 
Pen 2
Main PCA 
Pen 1
7
TB2
TB1
7
TB2
TB1
TB2
+
R
-
+
Calibration source
Copper
wires
24094
 
Figure 5-5  Calibration Set Up Diagram for Millivolts, Volts, and Milliamps Inputs