8.3.2  View Status of Tests 
Procedure 
The status of self-diagnostic tests can be viewed using the procedure in Table 8-3. 
Note that “FAILSF” is not a test. When “FAILSF YES” is displayed, it is an indication that the recorder is 
using the value of the control set up group “FAILSF” parameter as the output value because the recorder 
failed a self-test, or because the recorder detected an input failure while the input set up parameter 
“BRNOUT” = “NONE”.  
See Table 8-4 for more information about self-diagnostics, and for recommended actions when a test fails.  
 
Table 8-3  Procedure for Displaying the Results of Self-Diagnostics 
Step Operation  Press 
Action/Result 
Select STATUS 
set up Group 
SET 
 UP
 
Until you see: 
STATUS
Lower Display
READ
Upper Display
 
Read the status tests 
results 
FUNC
 
Until you see: 
Lower Display
Upper Display
FAILSF
NO or YES
YES indicates 
 a failure
 
•  Successive presses of the  FUNC   key will display 
the results of the status tests (PASS or FAIL) in the 
following order: 
 RAMTST 
 CFGTST 
 CALTST 
•  Identify the problem and correct the failure as shown