8.3.3 Background Tests 
Tests run automatically 
During normal operation of the recorder, tests of the configuration and calibration run in the background. If 
the recorder fails one of the tests, the appropriate message will be displayed as described in Subsection 
8.3.4. 
 
8.3.4 Error Messages 
All relevant messages are displayed 
If the recorder fails one or more tests, the operator is alerted by the display of one or more messages.
message is displayed at a time on the lower line of the display.  
If the problem is with the pen channel input or printed circuit assembly for which real time values are 
currently on display, the appropriate error message for each failed test will be displayed. The display will 
continue to cycle through the messages until the test is passed. 
If the failure is for the pen channel not on display, then a message will alert the operator to the existence of 
one or more error messages for the other pen. The message is “Pn ERR”, where n is the number of the pen 
with errors not on display. Once the operator has toggled the display to the pen channel whose input or 
printed circuit assembly was the source of the error, the display will cycle through the appropriate error 
messages. 
Error messages are listed in Table 8-4, along with the type of test to which each applies, the reason for the 
failure, and how to correct the problem. 
 
ATTENTION 
In addition to error messages, the recorder will display special status messages when optional features 
are active.  
•  If the lower display flashes “TUNING”, the recorder is in the process of automatically determining 
tuning parameters using the Accutune II feature described in Appendix D.   
•  If the lower display flashes “RUN n” or “HOLD”, the recorder is executing setpoint program “n” as 
described in Appendix C, and the run or hold action was initiated locally. 
•  If the lower display flashes “run n” or “hold”, the recorder is executing setpoint program “n”, and 
the run or hold action was initiated remotely. 
     
 
                                                           
If you are familiar with the operation of the recorder models without display, you are aware that in those models the 
red LED on the printed circuit assembly lights when the unit fails a self-diagnostic, or detects an out-of-range input.  
The red LED has a different function in the models with display and keypad. It is not an indication of a 
problem. In the models with display the red LED indicates that the display is currently interfacing with this PCA.  
Rely on the error messages to notify you of a problem with a recorder with a display. (The flashing green LED is an 