DR4300 Circular Chart Recorder 
226 
DR4300 Circular Chart Recorder Product Manual 
12/03 
D.2  Starting and Stopping Tuning with Accutune II 
Procedure 
After “TUNE” has been enabled in the tuning set up group as described in Section 4, use the procedure in 
Table D-1 to start tuning. 
To abort tuning in progress, press the MAN/AUTO/RESET key to take the recorder out of Auto mode.  
The message “AbRT” (abort) will be displayed as the value of tuning set up group parameter “AT ERR”.  
The tuning parameters will retain the values they had at the start of the Accutune operation. 
 
Table D-1  Procedure for Starting Accutune II 
Step Press 
Action/Result 
 DISP
 
until you see 
Lower Display
  TuneOF
 
If “TuneOF” (tune off) does not appear, then 
Accutune is not enabled. 
 
or 
 
to toggle to 
Lower Display
  TuneON
 Tuning will begin and the lower display will flash 
“TUNING”.  When tuning has been completed the 
lower display will again show “TuneOF”.