Appendix D - Using Accutune II  
12/03 
DR4300 Circular Chart Recorder Product Manual 
227 
D.3  Using Accutune with Duplex (Heat/Cool) Control 
Introduction 
“TUNE” can be done for applications using Duplex (Heat/Cool) control. 
During tuning, Accutune II assumes SP 1 will cause a Heating demand, and then the calculated tuning 
parameters will be automatically entered as the first set of PID constants. Likewise, it assumes tuning at 
Local SP 2 will cause a Cooling demand, and the cooling parameters will be entered as the second set of 
PID constants. 
 
Procedure 
After “TUNE” has been enabled in the tuning set up group as described in Section 4, use the procedure in 
Table D-2 to start tuning.  Note that control group parameter “NumSPs” must be set to “TWO” to enable 
the second setpoint. 
To abort tuning in progress, press the MAN/AUTO/RESET key to take the recorder out of Auto mode.  
The message “AbRT” (abort) will be displayed as the value of tuning set up group parameter “AT ERR”.  
The tuning parameters will retain the values they had at the start of the Accutune operation. 
 
Table D-2  Procedure for Using Accutune for Duplex Control 
Step Press 
Action/Result 
Heating Tuning 
 DISP
 
until you see 
Lower Display
  SP   nnn
 
Display Setpoint 1. 
 
or 
 
Until the value of Setpoint 1 is at the desired value within the Heat 
zone. 
Make sure the recorder is in Auto mode. (“A” indicator lit.) 
If not, use the MAN/AUTO/RESET key to put the unit in Auto. 
 DISP
 
until you see 
Lower Display
 UseSPn
  This is the prompt used to select the setpoint.  If 
it is not “USESP1”, use 
 or 
to switch to “USESP1”. 
 DISP
 
until you see 
Lower Display
  TuneOF
  If “TuneOF” (tune off) does not appear, then 
Accutune is not enabled. 
 
or 
 
to toggle to 
Lower Display
  TuneON
 Tuning will begin and the lower display will flash 
“TUNING”.  The output will cycle between 50 % 
and 100 % (or high output limit). When tuning has 
been completed the lower display will again show 
“TuneOF”. The Heat tuning parameters are 
entered for the first set of PID constants in the 
tuning set up group.