Pipe size example:
Given: -10°F Freezer with one system having (2) evaporators
•  One condensing unit rated at 24,000 BTUH’s @ -20°F SST R404A 
refrigerant.
•  Two evaporators each rated at 12,000 BTUH’s @ 10°F TD.
•  100 feet of actual line run between condensing unit to first evaporator  
and 20 feet of actual line run between the first evaporator and the 
second evaporator (see figure below).
How to figure line sizes:
Determine equivalent line run = actual run + valves and fitting allowances.
Use Line Sizing Tables to size lines.
Note any special considerations.
1.
2.
3.
Fittings in this system:
•  (6) 90° elbows in main line plus a 90° turn through a tee.
•  (5) addtional 90° elbows to first evaporator.
•  (4) additional 90° elbows to second evaporator.
Determine line size 1 (main line from condensing unit):
Main line from the condensing unit to be sized for the total capacity    
 
(balance) of the whole system of 24,000 BTUH’s (Table 8).
Refer to 24,000 @100 feet at -20°F SST R404A on the chart.    
 
 
You will find the suction line to be 1-3/8" and 1/2" liquid line.
Refer to Table 5. For every 1-3/8" 90° elbow you must add 4 equivalent    
 
feet of pipe and 2.5 equivalent feet of pipe for each 1-3/8" tee. 
 
 
Therefore, total equivalent line run = 
 
 
Actual line run 
 
100 feet 
 
 
+ (6) 1-3/8" elbows @ 4' 
24 feet 
 
 
+ (1) 1-3/8" tee @ 2.5'  
2.5 feet 
 
 
Total equivalent line run
12.5 feet
Refer to Table 8. For 126.5 total equivalent feet, the suction  
 
line size should be 1-3/8" and the liquid line stays at 1/2" line. 
 
Note: The gray shaded areas on Table 8. For 24,000 BTUH’s, the maximum 
suction riser is 1-1/8" to insure proper oil return and pressure drop from the 
bottom p-trap to the top p-trap.
1.
2.
3.
4.
Determine line size 2 (evaporators):
Line sizing to each evaporator is based on 12,000 BTUH’s and  
 
 
equivalent run from condensing unit. First evaporator has an 105 ft.  
 
 
run and the second evaporator has a 120 ft. run.
Table 8 indicates 1-1/8" suction for the first evaporator and indicates    
 
1-1/8" suction for the second evaporator.
Refer to Table 5. Each 1-1/8" 90° elbow adds 3 equivalent feet of pipe.     
 
Each 90° turn through a 1-1/8" tee adds 6 equivalent feet.
 
Actual line run (evap 1) 
105 feet 
 
 
+ (5) 1-1/8" elbows @ 3' 
15 feet 
 
 
+ (1) 90° turn through tee @ 6'  6 feet  
 
 
Total equivalent line run
12 feet  
Actual line run (evap 2) 
120 feet 
 
 
+ (4) 1-1/8" elbows @ 3' 
12 feet  
 
 
Total equivalent line run
12 feet
Table 8 indicates 1-1/8" suction line and 3/8" liquid line from  
 
 
main line to both evaporators.
1.
2.
3.
4.
5.
Unit Cooler Piping
Evap. 1
Evap. 2
Table . Weight of Refrigerants in Copper Lines During Operation (Pounds per 100 lineal feet of type "L" tubing)
Line Size O.D.
(Inches)
Refrigerant
Liquid Line
Hot Gas Line
Suction Line at Suction Temperature
-0˚F
-20˚F
0˚F
+20˚F
+0˚F
3/8
22
3.9
0.22
0.02
0.03
0.04
0.06
0.08
R507, 404A
3.4
0.31
0.03
0.04
0.06
0.09
0.13
1/2
22
7.4
0.41
0.03
0.05
0.07
0.11
0.15
R507, 404A
6.4
0.58
0.04
0.07
0.13
0.16
0.24
5/8
22
11.8
0.65
0.05
0.08
0.12
0.17
0.25
R507, 404A
10.3
0.93
0.07
0.11
0.17
0.25
0.35
7/8
22
24.4
1.35
0.10
0.16
0.24
0.36
0.51
R507, 404A
21.2
1.92
0.15
0.23
0.37
0.51
0.72
1-1/8
22
41.6
2.30
0.17
0.28
0.42
0.61
0.87
R507, 404A
36.1
3.27
0.26
0.39
0.63
0.86
1.24
1-3/8
22
63.5
3.50
0.27
0.42
0.64
0.93
1.33
R507, 404A
55.0
4.98
0.40
0.58
0.95
1.32
1.87
1-5/8
22
90.0
4.96
0.37
0.59
0.90
1.33
1.88
R507, 404A
78.0
7.07
0.56
0.82
1.35
1.86
2.64
2-1/8
22
156
8.61
0.65
1.03
1.57
2.30
3.26
R507, 404A
134
12.25
0.98
1.43
2.35
3.23
4.58
2-5/8
22
241
13.70
1.01
1.59
2.42
3.54
5.03
R507, 404A
209
18.92
1.51
2.21
3.62
5.00
7.07
3-1/8
22
344
18.95
1.44
2.28
 3.45
5.05
7.18
R507, 404A
298
27.05
2.16
3.15
5.17
7.14
9.95
3-5/8
22
465
25.60
1.94
3.08
4.67
6.83
9.74
R507, 404A
403
36.50
2.92
4.25
6.97
19.65
13.67
4-1/8
22
605
33.40
2.53
4.01
6.08
8.90
12.70
R507, 404A
526
47.57
3.80
5.55
9.09
12.58
17.80
Line Sizing
The following Tables 7 and 8 indicate liquid lines and suction lines for all 
condensing units for R22, R404A, and R507.
When determining the refrigerant line length, be sure to add an allowance 
for fittings. See Table 5. Total equivalent length of refrigerant lines is the sum 
of the actual linear footage and the allowance for fittings.