Heatcraft Refrigeration Products Condensing Units H-IM-CU User Manual

Page of 24
9
Liquid Lines
Liquid lines should be sized for a minimum pressure drop to prevent 
“flashing”. Flashing in the liquid lines would create additional pressure drop 
and poor expansion valve operation. If a system requires long liquid lines 
from the receiver to the evaporator or if the liquid has to rise vertically 
upward any distance, the losses should be calculated to determine whether 
or not a heat exchanger is required. The use of a suction to liquid heat 
exchanger may be used to subcool the liquid to prevent flashing. This 
method of subcooling will normally provide no more than 20
˚
F subcooling 
on high pressure systems. The amount of subcooling will depend on the 
design and size of the heat exchanger and on the operating suction and 
discharge pressures. An additional benefit from the use of the suction to 
liquid type heat exchanger is that it can help raise the superheat in the 
suction line to prevent liquid return to the compressor via the suction line. 
Generally, heat exchangers are not recommended on R-22 low temperature 
systems. However, they have proved necessary on short, well insulated 
suction line runs to provide superheat at the compressor.
Hot Gas Defrost Systems
Hot Gas Defrost systems can be described as reverse cycle, re-evap., or 
alternating evaporator.  Please see manual H-IM-HGD for Mohave™ systems.
Refrigerant Piping
Install all refrigerant components in accordance with applicable local and 
national codes and in accordance with good practice for proper system 
operation. The thermostatic expansion valve must be the externally 
equalized type. It can be mounted inside the unit end compartment. Mount 
the expansion valve bulb on a horizontal run of suction line as close as 
possible to the suction header. Use the clamps provided with the valve to 
fasten the bulb securely so there is a tight line-to-line contact between the 
bulb and the suction line. Suction and hot gas connections are made on the 
outside of the unit.
Suction lines should be sloped towards the compressor at the rate of one 
(1) inch per ten (10) feet for good oil return. Vertical risers of more than four 
(4) feet should be trapped at the bottom with a P-trap. If a P-trap is used, the 
expansion valve bulb should be installed between the unit and the trap.
Reverse Cycle System
The hot gas unit coolers can be used in reverse cycle hot gas defrost systems 
using multiple evaporators connected to one condensing unit. Generally, not 
more than one-third of the system defrosts at one time.  During the reverse 
cycle defrost, the reversing valve, located in the compressor discharge line, 
diverts hot gas through the suction line to the evaporator.
See the piping view in the Reverse Cycle Defrost Piping diagram. The suction 
line check valve directs the hot gas through the drain pan loop which 
prevents condensate in the pan from freezing. The hot gas exits the loop at 
the pan loop outlet header and enters the evaporator through the check 
valve assembly. As the hot gas defrosts the coil, heat is removed from the 
hot gas and eventually it condenses into a liquid and exits the coil at the 
distributor side port. The liquid then flows through the check valve of the 
thermostatic expansion valve bypass assembly, around the thermostatic 
expansion valve, and into the system liquid line. The liquid refrigerant then 
feeds other evaporators on the cooling cycle, evaporates, and returns to the 
compressor through their suction lines.
Hot gas line sizes for R-22, R0A and R507
System Capacity
BTU/Hr
Equivalent Discharge Length (Ft.)
25
50
75
100
150
4,000
1/2
1/2
1/2
1/2
1/2
5,000
1/2
1/2
1/2
1/2
1/2
6,000
1/2
1/2
1/2
5/8
5/8
7,000
1/2
1/2
5/8
5/8
5/8
8,000
1/2
5/8
5/8
5/8
5/8
9,000
1/2
5/8
5/8
5/8
5/8
10,000
1/2
5/8
5/8
5/8
5/8
12,000
5/8
5/8
5/8
7/8
7/8
14,000
5/8
5/8
7/8
7/8
7/8
16,000
5/8
5/8
7/8
7/8
7/8
18,000
5/8
7/8
7/8
7/8
7/8
20,000
5/8
7/8
7/8
7/8
7/8
25,000
7/8
7/8
7/8
7/8
1-1/8
30,000
7/8
7/8
7/8
1-1/8
1-1/8
35,000
7/8
7/8
1-1/8
1-1/8
1-1/8
40,000
7/8
1-1/8
1-1/8
1-1/8
1-1/8
45,000
7/8
1-1/8
1-1/8
1-1/8
1-1/8
50,000
7/8
1-1/8
1-1/8
1-1/8
1-1/8
60,000
1-1/8
1-1/8
1-1/8
1-3/8
1-3/8
70,000
1-1/8
1-1/8
1-3/8
1-3/8
1-3/8
80,000
1-1/8
1-1/8
1-3/8
1-3/8
1-5/8
90,000
1-1/8
1-3/8
1-3/8
1-5/8
1-5/8
100,000
1-1/8
1-3/8
1-3/8
1-5/8
1-5/8
Note:  Use next larger hot gas line size for -20
0
F. and lower suction temperatures.
EVAP. COIL 
TXV
PAN LOOP 
THREE-PIPE DEFROST PIPING
CHECK
VALVE 
HOT GAS LINE 
LIQUID LINE 
SUCTION LINE 
HEAT – X 
EVAP. COIL
TXV
PAN LOOP
CHECK VALVE
REVERSE CYCLE DEFROST PIPING
CHECK VALVE
CHECK
VALVE
LIQUID
LINE
SUCTION
LINE
HEAT – X
IMPORTANT:
It is imperative that with the alternating evaporator hot 
gas defrost system, no more that 25% of the operating 
refrigeration load be in defrost at any time.
Three Pipe System
The three pipe system (sometimes called re-evap.) uses three pipes: one for 
liquid line, one for suction line, and one for hot gas line. In addition, a re-
evaporator accumulator is used at the suction outlet of the evaporator. The 
hot gas is taken from the discharge line between the compressor and the 
condenser, through a hot gas solenoid valve, then to the evaporator drain 
pan circuit, distributor tee, through the coil. See the Three-Pipe Defrost
Piping Diagram for typical piping at the evaporator coil.
Alternating Evaporator System
In the alternating evaporator hot gas defrost system, a third line is taken 
off the compressor discharge line as the re-evap system. It is piped with 
solenoids at each evaporator, so that hot gas defrost is accomplished on one 
or more evaporators while the remaining evaporators continue to function 
in a normal manner. The liquid from defrosting evaporators is reintroduced 
to the main liquid line and it is necessary that 75% or greater capacity be 
retained in the normal refrigeration cycle to offset the capacity that is being 
removed by the units on the hot gas defrost.