Analog Inputs 
The analog input, DEMAND, has a current range of 4 - 20 mA. It is 
electrically isolated up to 500 VAC from the enclosure, 120 VDC power, 
digital I/O, and serial interface. The analog interfaces are not isolated from 
each other. See Figure 1-13 for a typical analog input connection. 
 
HFG2.0 
 
4-20mA INPUT
 
CONTROLLER 4-20 mA OUTPUT 
 
                                                           
+
 
                  
                               -
 
200
Ω
+
 
-
 
 
Figure 1-13.  Typical Analog Input Connection 
Analog Outputs 
The analog outputs, MOTOR CURRENT and POSITION, have a current 
range of 4 - 20 mA. They are electrically isolated up to 500 VAC from the 
enclosure, 120 VDC power, digital I/O, and serial interface. The analog 
interfaces are not isolated from each other. See Figure 1-14 for a typical 
analog output connection. 
 
CONTROL LER 4-20mA  INPUT
 
HFG2.0   4-20mA OUTPUT 
 
 + 
 
 -
 
<500
Ω
 
+
 
-
 
 
Figure 1-14.  Typical Analog Output Connection 
Discrete Inputs 
The discrete inputs are 24 VDC ON (High) and 0 VDC OFF (Low). They 
are electrically isolated up to 500 VAC. See Figure 1-15 for a typical 
discrete input connection. 
 
CONTROLLER DISCR ETE OUT PUT
 
HFG2.0  DISCRET E INPUT
 
 
Figure 1-15.  Typical Discrete Input Command Connection