22 HFG2.0 
USER 
GUIDE
 
 
FUNCTION 
Standard 9-Pin 
COM Port 
Standard 25-Pin 
COM Port 
Transmit  (Tx). 
Pin 3 
Pin 2 
Receive  (Rx) 
Pin 2 
Pin 3 
Ground  (GND) 
Pin 5 
Pin 7 
Table 1-5.  Computer COM Port Pin Outs 
WARNING 
Property Damage Hazard – The serial inputs are not electrically 
isolated 
. Failure to properly isolate the user serial interface 
could result in actuator or computer damage.  Use separate 
conduits for power and signal wiring. Close proximity to power lines 
may cause signal interference. 
Shock Hazard – The serial inputs are not electrically isolated 
If the power input is floating (not grounded), the serial input 
connections may have up to 120 VDC present. 
Property Damage Hazard – DO NOT connect 24 VDC power to any of 
the serial interface connections. 
 
Note: The pin designations shown in Table 1-5 are for the COM 
port on the computer. Make sure that the wiring to the 
COM port mating connector correctly matches Transmit 
from the HFG2.0 to Receive on the computer’s COM port, 
and vice versa. 
Note: The maximum distance for serial connections is 50 ft. This 
will typically only allow for local interface with a laptop PC.  
Note: The serial interface connections are not isolated
Isolation must be provided when connecting to a computer.