Hamilton Sundstrand Company Gas Fuel Metering Valve HFG2.0 User Manual

Page of 70
 
48 HFG2.0 
USER 
GUIDE
 
 
Fault Alarm Type 
Persist Time 
Fault Action 
 
 
Driver Over Current 
 
10 Sec 
 
 
 
1 Sec 
 
Driver current > Max Force equivalent 
current, Fault.  
 
 
Driver current > Max Force equivalent 
current, Fault. If persists for 1 Min., 
Shutdown 
 
 
Driver current > 18 Amps, Fault. If 
persists for 1 Min., Shutdown
 
 
 
Tracking Error 
 
10 Sec 
 
 
If in RUN state, not in home dead band 
and position error > allowable,  
Fault. 
 
 
If not in overcurrent, RDC not faulted and 
feedback not equal to demand, Fault. 
 
 
Watchdog Expired 
 
< 1 Sec 
If last reset was caused by watchdog 
timer timeout or illegal address attempt, 
Fault. 
RDC Failure 
< 1 Sec 
Tests hardware for RDC failure, sets 
Fault if RDC failure bit set. 
Retract/Extended 
Command 
N/A 
Fault not used. 
Unregulated Voltage Low 
10 Sec 
Unregulated voltage low, Fault. 
+14 Volts Low 
7.5 Sec 
 
< 1 Sec 
 
+14 V supply < 12 V, Fault.  
 
+14 Volts High 
7.5 Sec 
 
< 1 Sec 
 
 
+14 V supply > 16 V, Fault.  
 
-14 Volts Low 
7.5 Sec 
 
< 1 Sec 
 
-14 V supply > -12 V, Fault.  
 
-14 Volts High 
7.5 Sec 
 
< 1 Sec 
 
-14 V supply < -16 V, Fault.  
 
Input Voltage Low 
7.5 Sec 
 
< 1 Sec 
 
Input Voltage < 75 V, Fault.  
 
Input Voltage High 
7.5 Sec 
 
< 1 Sec 
  
Input Voltage > 180 V, Fault.  
 
DSP Failure 
N/A 
Fault not implemented. 
Electronics Over Temp 
10 Sec 
 Electronics 
temp 
≥ 110 °C, Fault 
 
Table 3-3.  Fault Configuration For FAULT Alarm