Emerson SS-100 User Manual

Page of 15
8 • UltraSite32 Setup as Alarm Receiver for SS-100
4
Reflecs
4.1.
UltraSite32 Setup as Alarm Re-
ceiver for SS-100
1.
Open UltraSite32 and add a site for the Reflecs 
controller that will be connected via Lantronix.
2.
Right-click on a site in the Tree View and select 
Edit Communications Information to open the 
Edit Site screen:
3.
Select the Network/Serial Gateway radio button 
under the Connection section along the bottom 
left of the screen.
4.
Enter the IP address for the Lantronix in the 
Address field and 3001 in the Port field under 
Network Settings.
5.
The site ID is used to match alarms to a site in the 
UltraSite32 database. Enter a site ID in the Site 
ID
 field. (Note that the site ID you enter must be 
unique. If the site ID entered is already assigned 
to another site, you will be prompted to enter a 
different site ID number.) Do Not leave the Site 
ID
 field blank: if left blank, no prompts to enter a 
different site ID number will appear, but the 
alarm receiving will not function correctly.
6.
Connect to the site and do a site inventory. This 
will send the site ID to the Reflecs box. Note: Be 
aware that if any user connects to this site from 
their own stand-alone UltraSite32 and they have 
a site ID configured, the site ID in the Reflecs 
will be overwritten. This will effectively break 
the alarm receiver setup. Although not manda-
tory, an access code could be set up for the site as 
a security measure.
7.
Open regedit from the Start menu and navigate to 
HKEY_CURRENT_USER\Soft-
ware\CPC\UltraSite32\Network
. Add a new 
dword value called ReflecsSerialGatewayLis-
tenPort
 and set it to the value of the port chosen.
8.
Close and restart UltraSite to save port settings.
4.1.1.
Troubleshooting
Close and restart UltraSite 32 if error messages regarding 
“failure to open a listening port” appear. This message 
indicates the port number is currently in use by another 
PC. Change the port number to one that is not in use.
4.2.
BCU
1.
Log on to the controller. 
2.
From the Main Menu screen, select 7. BCU Con-
fig 
to open the Configuration screen and 5. 
Remote Comm
 to access the RS-232 Communi-
cations Setup screen 
:
3.
Set LAN Adapter as the Dial-out Device.
4.
Enter the Dial Strings in the Dialout Phone #1 or 
the #2 field. The format is IpAddressHost-
Name:PortT
. For example, if the UltraSite32 
computer has a static IP address of 10.10.67.119 
and it is listening on port 3026, then the dial 
string would be 10.10.67.119:3026T. (Note that 
the dial string must end in the letter T.)
4.3.
BEC
1.
Log on to the controller. 
2.
From the Main Menu screen, select 7. Configu-
ration 
to open the Configuration screen and 5. 
                             Edit Site Screen in UltraSite
                      RS-232 Communications Setup Screen