Emerson SS-100 User Manual

Page of 15
SS-100 Serial Server
Reflecs • 9
Communications to access the Communications 
Setup screen 
:
3.
Set LAN Adapter as the Dial-out Device.
4.
Press 0 to go back to the Configuration screen.
5.
Press 3. System Information to open the BEC 
System Information screen.
6.
Press the down arrow once and the second BEC 
System Information screen is displayed:
7.
Enter the Dial Strings in the Phone number #1 
or the #2 field. The format is IpAddressHost-
Name:PortT
. For example, if the UltraSite32 
computer has a static IP address of 10.10.67.119 
and it is listening on port 3026, then dial string 
would be 10.10.67.119:3026T. (Note that the dial 
string must end in the letter T.)
4.4.
RMCC
1.
Log on to the controller.
2.
From the Main Menu screen, select 7. Configu-
ration 
to open the Configuration screen and 4. 
Remote Communication to access the Commu-
nications Setup screen 
:
3.
Set LAN Adapter as the Dial-out Device.
4.
Press 0 to go back to the Configuration screen.
5.
Press 3. System Information to open the RMCC 
System Information screen.
6.
Press the down arrow five times and the Dialout 
Setup screen is displayed:
7.
Enter the Dial Strings in the Day Phones 1 or 2 
fields or the Night Phones 1 or 2 fields. The for-
mat is IpAddressHostName:PortT. For exam-
ple, if the UltraSite32 computer has a static IP 
address of 10.10.67.119 and it is listening on port 
3026, then dial string would be 
10.10.67.119:3026T. (Note that the dial string 
must end in the letter T.)
                      BEC Communications Setup Screen
                        BEC System Information Screen
                     RMCC Communications Setup Screen
                                 RMCC Dialout Screen