2-4 Changing the Alarm Settings 
 
The values of alarm settings on this unit can be changed. The method for changing them is explained 
here. 
 
(1) Release the password lock. (Refer to 1-2 Releasing the Password Lock.) 
 
(2)  Press the AL switch until the alarm setting   
to be changed is displayed on the LCD display.   
(The bottom right of the screen, as in the table below.) 
The alarm setting for the actual gas concentration is 
displayed in the middle of the screen, and the 
percentage of the full scale value is displayed in the 
bottom right corner 
LCD Display 
Indication 
(Lower right) 
Default value 
Explanation of 
the default value 
Adjustable 
Range 
Toxic  : CDS-7 
Comb. : CHS-7 
A1  10 
10% F.S. 
A1  ** 
Oxygen: COS-7 
A2    72 
72% F.S. 
0 to 100% F.S. 
Toxic  : CDS-7 
Comb. : CHS-7 
A2  20 
20% F.S. 
A2  ** 
Oxygen: COS-7 
A2  76 
76% F.S.
 
0 to 100% F.S. 
* Pressing the AL switch changes to 1st level Æ 2nd levelÆ Normal display. 
* The A2 value should be greater than the A1 value in any case. 
 
(3) Press the special command switch. 
The setting to be changed and the    “—“ 
indication will then flash alternately. 
 
 
 
 
(4) Change the value by using the UP/DOWN key “U” and”V”. 
When you are done, press the special command switch again, and the alternating display in the lower 
right corner of the LCD display will become constant. The process is now finished. 
 
(5) When this is finished, press the UP/DOWN switches (“U” or”V”) again to return to the normal display. 
 
Note 
The relationship between 1
st
 level and 2
nd
 level alarm values of each alarm mode is as follows: 
AL switch 
The percentage of the full scale value
Gas concentration
- - - - - 
A1 10
Special 
command 
switch 
UP/DOWN switches