Motor Setup Guidelines 
80 
 
 
Once the Encoder Decode is verified, increment Ixx61 gradually and redo the Open-Loop test 
until a solid saw tooth response is observed. Note that further increasing Ixx61 will not improve 
the performance.     
 
Correct Encoder Decode-Acceptable Open-Loop Response 
 
 
Position-
Loop PID Gains: Ixx30…Ixx39 
The position-loop tuning is done as in any Turbo PMAC PID-Loop setup. The 
PMACTuningPro2 automatic or interactive utility can be used to fine-tune the PID-Loop. 
Acceptable Step and Parabolic position responses would look like: