Delta Tau GEO BRICK LV User Manual

Page of 271
Geo Brick LV User Manual
 
PinOuts and Software Setup 
 140 
Setting up the General Purpose Relay, Brake 
This  option  provides  either  a  general  purpose  relay  (which  can  be  toggled  in  software)  OR  a  dedicated 
brake relay  output tied to  its’ corresponding channel  amplifier-enable  line. This  option  is built to  order 
and is jumper configurable at the factory (E6, E7, E8 and E9). 
 
The brake relay  is commonly used in synchronizing (in  hardware)  external  events such as automatically 
releasing a motor brake upon enabling it (i.e. vertical axis). In this mode, the general purpose relay has no 
use, and the related registers (suggested M-variables) are meaningless. 
 
!
Caution 
This option utilizes the 
 relay, which is rated to up to 
220VAC.  However,  it  is  advised  to  use  an  external  relay  for  AC 
operations, and limit the usage for this connection to up to 30VDC at 
2 amperes. 
 
The brake output can be either: 
 
 
High true using the normally open contact (pin #9) 
 
Low true using the normally closed contact (pin #4) 
 
Also, it can be either sourcing or sinking depending on the wiring scheme. 
 
The following table summarizes the logic of operation: 
Operation 
Command From 
Geo Brick LV 
Contact between pins 
#8 and #9 
Contact between pins 
#8 and #4 
Brake 
Amp. disabled (killed) 
Open 
Closed 
Amp. Enabled (open/closed loop) 
Closed 
Open 
GP Relay 
M-variable = 0 
Open 
Closed 
M-variable = 1 
Closed 
Open