Geo Brick LV User Manual
 
PinOuts and Software Setup 
 143 
X13: USB 2.0 Connector 
This  connector  is  used  to  establish  USB  (A-B  type  cable)  communication  between  the  host  PC  and  the 
Geo  Brick  LV.  This  type  of  USB  cable  can  be  purchased  at  any  local  electronics  or  computer  store.  It 
may be ordered from Delta Tau as well.  
 
Pin #  Symbol  Function 
VCC 
N.C.
 
D- 
Data-
 
D+ 
Data+
 
Gnd 
GND
 
Shell 
Shield
 
Shell 
Shield
 
 
!
Caution 
The  electrical  ground  plane  of  the  host  PC  connected  through  USB 
must  be  at  the  same  level  as  the  Geo  Brick  LV.  Ground  loops  may 
result  in  ESD  shocks  causing  the  damage  of  the  communication 
processor on the Geo Brick LV.    
 
 
Note 
Use  a  shielded  USB  (category  6  or  7)  cable.  In  noise  sensitive 
environment, install ferrite cores at both Geo Brick and PC side. 
 
If the electrical ground planes of the host PC and the Geo Brick LV are not at the same level (e.g. laptop 
on battery) then the use of an industrial USB hub is highly advised.   
 
X14: RJ45, Ethernet Connector 
This connector is used to establish communication over Ethernet between the PC and the  Geo Brick LV. 
A  crossover cable is required  if  you are  going  directly to the Geo  Brick LV  from the PC Ethernet card, 
and not through a hub. 
Delta  Tau  strongly  recommends  the  use  of  RJ45  CAT5e  or  better  shielded  cable.  Newer  network  cards 
have  the  Auto-MDIX  feature  that  eliminates  the  need  for  crossover  cabling  by  performing  an  internal 
crossover when a straight cable is detected during the auto-negotiation process. For older network cards, 
one  end  of  the  link  must  perform  media  dependent  interface  (MDI)  crossover  (MDIX),  so  that  the 
transmitter  on  one  end  of  the  data  link  is  connected  to  the  receiver  on  the  other  end  of  the  data  link  (a 
crossover/patch  cable  is  typically  used).  If  an  RJ45  hub  is  used,  then  a  regular  straight  cable  must  be 
implemented. Maximum length for Ethernet cable should not exceed 100m (330ft).