Delta Tau GEO BRICK LV User Manual

Page of 271
Geo Brick LV User Manual
 
Motor Setup 
 187 
Absolute Power-On Phasing: EnDat | SSI | BiSS 
With absolute serial encoders, the absolute serial data can be used to establish a phase reference position 
on power-up without moving the motor or executing a phase search move. 
The  automatic  setup  of  power-on  phasing  with  PMAC  is  established  through  finding  the  motor’s  phase 
offset (a one-time test per installation) and storing the result (scaled properly) in the phase position offset 
register (Ixx75). It also requires specifying the power-on phase source (Ixx81), and format (Ixx91).   
The following, is a summary of the settings with the various proposed setup techniques: 
 
 
Technique 1 
Technique 2/3 
(Ixx01=1) 
 
For Ixx01= 3 
For Ixx01= 1 
PhaseOffset 
(found experimentally) 
Read from 
Serial data register A 
Read from 
Position ECT result 
Read from 
Commutation ECT result 
Ixx81 
= Serial data register A  = Ixx83 (Pos. ECT result) 
= Comm. ECT result 
Ixx91 
= Unsigned, Y-register 
ST bits 
= Unsigned, X-register, 
(ST + 5bit shift) bits 
= Unsigned, X-register, 
18 bits 
Ixx75 
= ( - PhaseOffset * Ixx70 ) % Ixx71 
 
 
Note 
The  automatic  power-on  phasing  routine  (Ixx75,  Ixx81,  and  Ixx91) 
expects the least significant bit of the data to be right most shifted (at 
bit 0). 
 
Remember that the serial data register A address for each of the channels is: 
 
Serial Data Register A 
Channel 1  Y:$78B20  Channel 5  Y:$78B30 
Channel 2  Y:$78B24  Channel 6  Y:$78B34 
Channel 3  Y:$78B28  Channel 7  Y:$78B38 
Channel 4  Y:$78B2C  Channel 8  Y:$78B3C 
 
!
Caution 
Prior  to  implementing  an  absolute  power-on  phasing  routine,  make 
sure that the motor can be phased manually, and that open-loop and/or 
closed-loop  moves  (require  PID  tuning)  can  be  performed 
successfully.