Motor Setup 
 188 
Finding the Phase Offset 
The  phase  offset  is  found  experimentally  by  performing  a  one-time  phase  force  test  on  an 
uncoupled/unloaded (preferably) motor: 
 
1.  Read/update the absolute position (must be read correctly for the phasing to work).  
Issue a #n$* command, or enable the corresponding absolute position read PLC. 
2.  Record Ixx29, and Ixx79 (if non zero).These should be restored at the end of the test 
3.  Set Ixx29=0, and write a positive value to Ixx79 (500 is a good starting value). 
4.  Issue a #nO0 to send a zero open loop output. 
5.  Increase Ixx79 until the motor is tightly locked onto a phase. 
6.  Make sure the motor is settled and stationary (locked onto a phase) 
7.  Record the following value (this is the motor’s phase offset): 
Technique 1 
Technique 2/3 
For Ixx01=3 
For Ixx01=1 
Query the motor’s corresponding 
serial data register A  
e.g. RY:$78B20 
Query the motor’s corresponding 
position ECT result 
e.g.: RX:$3502 
Query the motor’s corresponding 
commutation ECT result 
e.g.: RX:$3512 
 
 
 
 
8.  Issue a #nK to kill the motor 
9.  Restore Ixx29, and Ixx79 to their original values 
 
Setting up Ixx81, the power-on phase position address: 
Technique 1 
Technique 2/3 
(Ixx01=1) 
For Ixx01= 3 
For Ixx01= 1 
= Serial data register A 
= Ixx83 (Pos. ECT result) 
= Comm. ECT result 
 
 
Technique 1: 
 
If Ixx01= 3; 
Ixx81 is equal to the motor’s corresponding serial data register A. (e.g.: I181=$78B20). 
If Ixx01=1; 
Ixx81 is equal to the motor’s corresponding position ECT result. (e.g.: I181=$3502). 
 
 
Technique 2/3:   
Ixx81 is equal to the motor’s corresponding commutation ECT result. (e.g.: I181=$3512).