PinOuts and Software Setup 
 42 
For Help with clock calculations, download the Delta Tau Calculator: 
  
 
J9 Analog Output Suggested M-Variable 
// I/O 10 & 11 Mode (PWM) 
M7051->Y:$78404,10,1 
M7052->Y:$78404,11,1 
M7051=0  
; =0 PWM, =1 PFM 
M7052=0  
; =0 PWM, =1 PFM 
 
// Analog Output M-variable  
M7050->Y:$78412,8,16,S 
 
// These I/O nodes have to be setup once on power-up.  
// power-up PLC Example 
Open PLC 1 clear 
I6612=100*8388608/I10 While(I6612>0) Endw 
M7051=0 ; PWM mode 
M7052=0 ; PWM mode  
Disable PLC 1 
Close 
 
Testing the J9 Analog Output 
With I6800=735, writing directly to the assigned M-variable (i.e. M7050) should produce the following: 
 
M7050 
Single-Ended: 
Gnd  Output+ 
Differential: 
Output+  Output- 
-735 
-10V 
-20V 
-368 
-5V 
-10V 
0V 
0V 
368 
+5V 
+10V 
735 
+10V 
+20V 
 
 
 
Note 
Writing values greater than I6800 (i.e. 735) in M7050 will saturate the 
output  to  10,  or  20  volts  in  single-ended  or  differential  mode 
respectively   
 
 
Note 
MACRO connectivity provides more analog output options, e.g. ACC-
24M2A.