Delta Tau GEO BRICK LV User Manual

Page of 271
Geo Brick LV User Manual
 
PinOuts and Software Setup 
 61 
X1-X8: Encoder Feedback, Resolver 
 
X1-X8: D-sub DA-15F 
Mating: D-sub DA-15M 
2
3
4
5
6
7
8
9
10
11
12
13
14
15
1
 
Pin # 
Symbol 
Function 
Notes 
Sin+ 
Input 
Sine+ 
Cos+ 
Input 
Cosine+ 
CHC+ 
Input 
Index+ 
EncPwr 
Output 
Encoder Power 5 Volts 
 
 
Unused 
 
 
Unused 
2.5 Volts 
Output 
Reference Power 2.5 volts 
 
 
Unused 
Sin- 
Input 
Sine- 
10 
Cos- 
Input 
Cosine- 
11 
CHC- 
Input 
Index- 
12 
GND 
Common 
Common Ground 
13 
 
 
Unused 
14 
 
 
Unused 
15 
ResOut 
Output 
Resolver Excitation Output 
 
This option allows the Brick to connect to up to eight Resolver feedback devices. 
 
Setting up Resolvers 
The  Resolver  data  sampling  is  done  at  phase  rate,  and  processed  in  the  encoder  conversion  table.  The 
commutation (occurring at phase rate) position is retrieved from the Encoder Conversion Table which is 
normally read at Servo rate. Thus, the Servo and Phase cycles have to be at the same rate.   
 
 
Note 
 
Use  an  encoder  cable  with  high  quality  shield.  Connect  the 
shield to chassis ground, and use ferrite core in noise sensitive 
environment if deemed necessary. 
 
It  is  essential  to  set  the  Servo  clock  the  same  as  the  Phase 
Clock in Resolver applications. This will greatly reduce noise. 
 
The  Servo  Cycle  Extension  Period  (Ixx60)  can  be  used  to 
lower the CPU load and avoid quantization errors through the 
PID loop at high Servo rates.