Emerson E2 User Manual

Page of 283
The 16AI, 8IO, and MultiFlex Inputs
Input and Output Setup
 • 
9
-
7
ital, or press 
 to cancel setup.
Figure 9-5
 - Data Type Pop-Up Menu
Depending upon what type of input you selected, the 
Analog Input or the Digital Input screen will appear. The 
analog screen is described in Section 9.1.3.3, while the 
digital screen is described in Section 9.1.3.4.
9.1.3.2
Using the Input Definitions/
Status Screen
In order for the E2 to properly read an input value from 
a sensor or transducer hooked to an I/O board, you must 
first tell the E2 what kinds of devices are hooked into each 
input board point. This is achieved by using the Input 
Definitions/Status screen. 
 (SETUP),  (DEL/
MOD), 
 (OFFSET),  (LOOK UP), and  
(CANCEL) are the function keys along the bottom of the 
screen available for the Input Definitions/Status screen.
Each record in this screen contains the following infor-
mation about a point:
1. Type (read-only)
The Type column will read 16AI regardless of whether 
the input board is a 16AI, MultiFlex 16, 8IO, or MultiFlex 
Combination I/O board. 
 2. Board (read-only)
The point’s board number will appear in its point 
record under the Board column. All input boards on a 
controller will be displayed.
3. Point (read-only)
The point number of each point appears in its record 
under the Point column.
4. Type (read-only)
The Type field shows the output’s data type. Possible 
Types are: A (Analog) or D (Digital). If the point has not 
been identified, a “-” will appear in the field instead.
5. Application
 Select which application you wish to set up inputs to. 
Pressing 
 (LOOK UP) when on a defined point will 
open the Application Selection menu--a list of application 
types currently existing in the box. 
 (CANCEL) will 
cancel this menu.
6. Association
If a point has already been defined and is currently 
being used by an application, the name of the input to 
which the point is connected will be displayed in the Asso-
ciation
 field.
Association is the application’s user-defined property 
that is associated with the point. Multiple applications 
attached to single input will all be displayed in the Associ-
ation
 field. Pressing 
 (LOOK UP) on a set applica-
tion will bring up a list of property selections. 
 
(CANCEL) will cancel this menu.
7. Value (read-only)
Value shows the sensor value in the units you select for 
the input type.
9.1.3.3
Setting Up Analog Inputs
Open the Analog Input screen by selecting an Analog 
(A) input from the Input Status screen Figure 9-4 and 
pressing 
 (SETUP).
types, units, and default values are specified for analog 
input points.
NOTE: When setting up 88s and 8AOs, re-
member that there are only eight usable input 
points, even though the 16AI that represents 
the 88s and 8AOs in the summary screen has sixteen 
points. Only inputs one through eight (1-8) may be de-
fined; all other points will be ignored. 
This is also true of 168DOs and 1616DOs. The Multi-
Flex 168DO’s and 1616DO’s digital output’s position 
appears as an 8DO, but only the first four outputs are 
usable.
NOTE: When changes are made to the Appli-
cation or Association fields, data will not be 
saved until attempting to arrow off of that par-
ticular board and point or attempting to leave the 
screen. If Type has changed, data will be saved and then 
the controller will take you to the Setup In screen.