10 Quick Start
This section covers what to do when you are program-
ming a new E2 for the first time. The section includes log-
ging on, specifying information about I/O boards and 
application types, and other topics related to E2 program-
ming and navigation.
10.1 Logging On
Figure 10-1
 - User Login Dialog Box
When the E2 is powered up for the first time, the first 
screen displayed after initialization is the User Login 
screen. 
1.
Enter “USER” in the Username field.
2.
Press 
.
3.
Enter “PASS” in the Password field.
4.
 Press 
.
Logging into and out of the E2 controller can be done 
at any time by pressing the 
 key on the E2 keypad. If 
you are currently logged out, pressing 
 will bring up 
the User Login dialog box. If you are already logged in, 
pressing 
 will immediately log you out and return 
you to the E2 home screen.
10.2 Cleaning Out the 
Controller
Cleaning out the E2 controller needs to be done if:
•If you are programming your E2 controller for 
the first time. 
•If all of the settings need to be cleared.
•If the program settings are unknown.
Open the E2 controller panel. There are two buttons 
located midway down on the main board (see Figure 2-2). 
These buttons are used to perform various hardware func-
tions.
Reset Button - The button 
labeled "RESET" on the main 
board resets the controller. 
Pressing and holding this button 
for one second will cause the E2 
to reset and retain all pro-
grammed applications, logs, and 
other data stored in memory.
Clean Out Button - The button labeled CLEAN OUT 
on the controller is used to perform a function called clean 
out
. Using this button in conjunction with the Reset But-
ton will cause a clean out, which is a reset that erases all 
data from memory
. The E2 will re-boot after a clean out 
with all programmed applications, logs, and other data 
erased.
Clean outs are also commonly called Blue “R” resets, 
named for the key presses required to clean out Emerson 
Retail Solutions’ previous generation of controllers, 
REFLECS.
Performing a Clean Out
CAUTION: A clean out will erase all pro-
grammed parameters from memory. Do not 
follow these instructions unless you are abso-
lutely sure you wish to remove all applications and logs 
from memory.
1. Press and RELEASE the 
Reset Button quickly. The 
screen will clear.
2. Press and Hold the Clean Out 
button.
3.When “CLEANOUT” appears 
in large text across the screen, 
RELEASE the Clean Out but-
ton.