Emerson E2 User Manual

Page of 283
3-8
 • 
E2 RX/BX/CX I&O Manual 
3.5.4 Insertion Temperature Probe
3.5.4.1
Location
The 12-inch insertion temperature probe may be used 
to monitor temperature in either the supply or return air 
ducts of the AHU or RTU.
3.5.4.2
Mounting
The insertion probe may be mounted in any orientation 
within the duct as long as the probe is in the air flow of the 
duct. The probe housing should be secured using self-tap-
ping screws. A 0.250” diameter hole is required for the 
probe. Figure 3-21 shows the installation of the insertion 
probe (self-tapping screws are not provided).
Figure 3-21
 - 12-Inch Insertion Probe Mounting
3.5.5
Supply and Return Air 
Sensors
In addition to the 12-inch insertion temperature probe, 
Emerson Retail Solutions uses the same temperature sen-
sor used for outside and inside temperature to monitor sup-
ply and return air temperature. When used in this 
application, the sensors are supplied without enclosure 
covers. The sensors should be mounted directly in the air 
stream of the supply or return air duct. The sensors are not 
supplied with any mounting hardware for this application.
3.5.6
Refrigeration System 
Temperature Probes and Sensors
3.5.6.1
Location
Emerson Retail Solutions supplies several temperature 
monitoring devices including bullet sensors, pipe mount 
sensors, immersion probes, insertion probes, and sensors 
for high temperature applications. Each of these sensors is 
generally installed on the system by the equipment manu-
facturer. If a device must be added to the system, refer to 
the information supplied with the device and consult the 
refrigeration equipment manufacturer. Table 3-1 lists some 
typical sensor applications and the sensor or probe most 
suited for that purpose.
Table 3-1
 - Sensor Application and Type
Application
Sensor Type
Condenser Outlet (Drop Leg)
High Temperature 
Bullet
Liquid (Manifold)
Pipe Mount
Suction Temperature
Pipe Mount
Discharge Air
Bullet
Ambient Temperature (Out-
side)
Bullet
Condenser Sump
Insertion Probe
Defrost Termination
Bullet
3.5.6.2
Mounting Bullet and Pipe Mount 
Sensors
Bullet or pipe mount sensors mounted on refrigerant 
lines should be secured with a Panduit low temperature 
cable tie, number PLT2S-M120, or equivalent. For pipe 
mount sensors, the curved surface should be placed 
against the pipe and the tie should be positioned in the 
groove on the top surface of the sensor. A second tie 
should be used to secure the lead to the pipe for additional 
support.
Sensors located on refrigerant lines should be insulated 
to eliminate the influence of the surrounding air. A self-
adhering insulation that will not absorb moisture is recom-
mended to prevent ice logging at the sensor location.
The sensor should be positioned on the side of the line 
as shown in Figure 3-22.
Figure 3-22
 - Sensor Orientation