Emerson E2 User Manual

Page of 283
2
4VA
1
40VA
+
48VA
=
8-4
 • 
E2 RX/BX/CX I&O Manual 
2.
Use a transformer that has a power rating 
equal to or higher than the total calculated 
VA (see Table 8-3).
Example: Boards totaling 48VA can be connected to 
either a 50VA or 75VA transformer.
Table 8-4
 - Device Power Requirements
Unit
amps
VA
VAC
Center 
tapped?
E2
1.66
40
24
No
ESR8
2.4
75
24
No
TD3
0.11
4
24
No
CC-100/
CS-100
Power supplied by Power Module
Refer to the installation guides on the next few pages 
for instructions on how to install these boards on the Eche-
lon Network.
8.7
LEDs
The Echelon Board LEDs can be used to determine the 
status of normal operating parameters for the board.
Table 8-5 - Echelon LED Status
Echelon Board
Status
Red (D1) (Reset)
ON: The Echelon port is being 
held in reset or if momentary it 
means the board has gone 
through reset
Red (Service)
During normal operation this 
LED should be off. If the Service 
Pin is pressed, this LED will 
come on.
If the LED is blinking, the node 
does not have its Subnet/Node 
address set. (E2 should set this 
during the first power -up se-
quence where the user will be 
asked in which Subnet to put the 
controller (E2 will always be 
Node = 1 on the network). 
If the LED is blinking, then try 
resetting the E2. If this does not 
correct the problem, replace the 
Echelon board.
ON (no blinking): Replace the 
Echelon board. The Neuron pro-
cessor has lost its application 
program.
8.8
Open Echelon Device 
Connectivity
Open-Echelon E2s must be ordered pre-configured 
from Emerson Retail Solutions. Open-Echelon licenses 
must be purchased and enabled on units, and are not trans-
ferrable to other units without assistance from Emerson 
Retail Solutions. Call 770-425-2724 for technical assis-
tance or your sales representative. Your sales representa-
tive will know which devices your unit will connect to. 
8.8.1
Configuring Echelon Devices
Login to the controller and enter the desired number of 
Echelon devices to be added in the Connected I/O screen. 
From the Main Menu:
1.
 Select
 
 (System Configuration)
2.
 Select
 
 
(Network Setup)
3.
 Select
 
 
(Connected I/O Boards and Control-