WARNING
: United States regulations forbid 
installing the unit within 4’ of any opening into any 
building.  Similar Canadian regulations forbid the 
unit from being installed within 10’ of any opening 
into any building.  
 
 
 
 
 
WARNING
: Improper installation can cause 
nausea or asphyxiation from carbon monoxide and 
flue gases which could result in severe injury or 
death. For installation in altitudes above 4,500 
feet, contact the manufacturer for instructions. 
 
Indoor Installation 
Follow all local codes, or in the absence of local 
codes, follow the codes for Installation of Gas 
Burning Appliances; National Fuel Gas Code ANSI 
Z221.23 in USA or CAN/CGA B149.1 or .2 in 
Canada. 
 
WARNING
In an indoor installation, the T-K1S 
must be connected to a Category III special gas 
vent in order to direct the dangerous exhaust 
byproducts to the outdoors. Connect the 4” 
Category III vent pipe to the 4” round collar on the 
top of the unit. 
 
WARNING
Do not install the unit directly on a 
combustible surface such as carpeting, wood 
floors, etc.  If it is necessary to install the unit 
standing on a surface, install a 3” noncombustible 
base between the unit and the surface. 
 
Combustible Air Supply 
The T-K1S must be installed in a location where 
the proper amount of combustible air will be 
available to it at all times.  If the unit is installed in 
a confined space, there must be permanent 
openings supplying air to the unit. 
If the openings will bring air directly from the 
outdoors, two openings are required, and they 
should be sized to give a minimum free area of 
one square inch for every 4000 BTUH of the 
maximum input rating of the unit.   
If the openings will bring air from another indoor 
area, they should be sized to give a minimum free 
area of one square inch for
 
every 1000 BTUH of 
the maximum input rating of the unit. One of these
 
openings should be within 12” of the ceiling, and 
the other should be within 12” of the floor.