PART 6 – VENTING, COMBUSTION AIR, AND CONDENSATE REMOVAL 
 
The boiler must be vented as detailed in this Venting Section. Ensure exhaust vent and intake piping complies with these instructions 
regarding vent system. Inspect finished exhaust vent and intake piping thoroughly to ensure all joints are well secured, airtight, and 
comply with all applicable code requirements, as well as with the instructions provided in this manual. Failure to properly install the vent 
system will result in property damage, severe personal injury, or death. 
A. GENERAL 
 
This boiler is certified as a “Category IV” appliance, and requires a special venting system. The vent system will operate with a positive 
pressure in the pipe. Exhaust gases must be piped directly outdoors using the vent materials and rules outlined in these instructions. 
Do not connect vent connectors serving appliances vented by natural draft into any portion of mechanical draft systems operating under 
positive pressure. Follow the venting instructions below carefully. Failure to do so will result in substantial property damage, severe 
personal injury, or death. 
 
1. Installation should be made in accordance with the regulations of the Authority Having Jurisdiction, local code authorities, and utility 
companies which pertain to this type of water heating equipment. 
 
2. Install the venting system in accordance with these instructions and with the National Fuel Gas Code, ANSI Z223.1/NFPA 54, 
CAN/CGA B149, and/or applicable provisions of local building codes. 
 
3. This boiler must be vented with materials, components, and systems listed 
and approved for Category IV boilers. 
 
 
Exhaust vent and intake pipes are to be piped separately. This boiler 
cannot share a common exhaust or intake with multiple appliances. Failure 
to follow this instruction will result in substantial property damage, severe 
personal injury, or death. 
 
NOTE: To avoid contamination often contained in indoor air, it is best to pipe all 
intake combustion air directly to the outdoors. 
 
NOTE: If exhaust vent pipe system passes through an unheated space, such as 
an alcove or attic, the space must be heated or the pipe must be insulated. The 
insulation must have an R value sufficient to prevent freezing of the 
condensate. 
 
 
Failure to follow all instructions can result in flue gas spillage and carbon 
monoxide emissions, causing severe personal injury or death. 
 
 
Improper seating of vent pipe gaskets can cause eventual gasket failure and exhaust gas leakage. Ensure the exhaust vent is properly 
beveled and seated before insertion into the flue adapter. Failure to do so could result in property damage, severe personal injury, or 
death. 
 
 
Due to the extreme flammability of most glues, cements, solvents, and primers used to join plastic exhaust and intake pipes, explosive 
solvent vapors must be cleared from all vent piping before start-up. Avoid using excess cement or primer, as this may pool in the vent 
pipes. Vent assemblies should be allowed to cure for a period of at least 8 hours before powering a connected appliance. Failure to 
follow these instructions will result in substantial property damage, severe p
ersonal injury, or death. It is the installers’ responsibility to 
understand the hazards associated with explosive solvents and take the necessary precautions to avoid these risks.