ENTER key to accept the code entered. If the code is correct, the readout will change to the appropriate screen. If the programming 
code is not accepted, the readout will continue to display as shown above. 
 
The ENTER key is also used to enable a function for editing. After the user navigates to the desired function, the user would hold down 
the ENTER key for one second. When the ENTER key is released, the function value will begin to blink. The function can now be 
changed using the 
▼▲ ARROW keys. After the new value is displayed, the user then presses the ENTER key for 1 second to lock the 
new value of the function in. The value will then stop blinking. 
 
LEFT AND RIGHT ARROW KEYS 
–    are used to navigate between the default display, status display, analog and cascade dis-
plays if they are enabled. The   keys are also used in programming modes to change between the programmable functions. It is 
recommended you use the Menu Maps in the back of this manual and the detailed menu instructions printed in this section to help in 
menu navigation. 
 
UP AND DOWN ARROW KEYS 
– ▼▲ are used to navigate between the various functions displayed in the menu. After the function is 
enabled for editing by pushing the ENTER key, the 
▼▲ keys are used to adjust the function upward or downward to the desired value. 
C. OPERATING INSTRUCTIONS 
Before operating the boiler, it is important to remove the cover and verify that the gas line and water lines are connected to boiler and 
fully purged. If you smell gas, STOP; Follow the safety instructions listed in the first part of this section. If you do not smell gas, follow 
the next steps. 
  
1. Turn down the thermostats before applying power to the boiler. If 0
–10 volt or other inputs are used, make sure that they are set so 
there is no call for heat while programming.  
 
2. Turn on the power to the boiler or boilers if a cascade system used.  
 
3. Next, check the boiler settings. Adjustment and factory defaults are outlined within this section. If a cascade system is used, it is 
important that all the boilers have the same boiler settings.  
 
4. Next, check the system settings. Adjustments and factory defaults are outlined within this section. If a cascade system is used, it is 
important that the Master Boiler is programmed with the correct system settings. 
 
5. Create a demand on the boiler or boilers if a cascade system is used. The user can monitor system functions when the boilers are 
operational.  
 
6. If the boilers fail to start, refer to the troubleshooting section in the back of this manual. 
D. PROGRAMMING BOILER SETTINGS  
Boiler Setting Program Access  
NOTE:
 Programming the boiler control is not possible when the boiler is firing. Make sure any input which can create a demand on the 
boiler, such as the tank thermostat, is turned off, so the boiler will remain idle to allow programming. 
 
SCREEN 
DESCRIPTION 
ENTER   MENU   CODE 
000 
To access the boiler setting program, press and hold the ENTER Key for 4 seconds, until the display shows the screen 
at left.
 
 
ENTER   MENU   CODE 
600 
Using the arrow keys, log in the Boiler 
Menu Access Code “600”. To confirm the code, press ENTER to access 
Boiler Setting Program navigation menu.
 
Table 17 
– Programming Screens 
Boiler Setting Program Navigation 
Once the code is confirmed, the user can now start to set the Boiler Settings. Use the arrow keys on the display to navigate through 
the Boiler Setting Program. A blinking setting indicates it can be changed. To change a setting, press the ENTER Key. Boiler settings 
can be increased by pressing the UP ARROW 
▲ and decreased by pressing the DOWN ARROW ▼ on the display. When done, press 
ENTER. Setting will stop blinking and you can move on to next setting. Press RESET to exit programming and store settings. Listed 
below are the boiler settings that can be programmed into the control. 
 
SCREEN 
DESCRIPTION 
CENTRAL HEAT 
180 
o
Function: Adjusts the boiler set point. Default: 180
o
F (Range: 50
o
F to 190
o
F).
 
 
CENTRAL DIFF SET 
30 
o
Function: Adjusts the boiler differential set point. Default: 30
o
F (Range: 5
o
F to 30
o
F).