Westinghouse WBCNG399WPU Installation Instruction

Page of 90
65 
 
 
 
WHL-016 REV. 3.4.15 
DHW   SET  POINT 
119  
o
Function: Adjusts the indirect tank set point. Default: 119
o
F (Range: 70
o
F to 185
o
F).
 
 
 
DHW   DIFF  SET  POINT 
7  
o
Function: Adjusts the indirect tank differential set point. Default: 7
o
F (Range: 1
o
F to 30
o
F).
 
 
TEMP   DISPLAY C  OR F 
      
o
Function: Adjusts the temperature measurement in F = Fahrenheit to C = Celsius (Default is Fahrenheit).
 
Table 18 
– Boiler Setting Screen Descriptions 
Clock Settings 
(NOTE: The clock will reset if the boiler is powered off for more than a week.) 
 
SCREEN 
DESCRIPTION 
CLOCK  MODE         (12/24) 
08/28/2009             Fr  9:42A 
Function: Changes the clock from 12 hour mode (8:45 PM) to 24 hour mode (20:45). To change to 24 hour mode, 
press the ENTER key. The letter (A or P) after the time will blink. Press the up or down arrow key once and the letter 
will disappear. Press the ENTER key to save the new setting.
 
 
CLOCK  HOUR                        
 08/28/2009          Fr  10:01A 
Function: Allows the user to adjust the hour setting.
 
 
CLOCK  MINUTE                        
 08/28/2009          Fr  10:01A 
Function: Adjusts the minute setting.
 
 
CLOCK  DAY  OF  WEEK                        
 08/28/2009          Fr  10:01A 
Function: Adjusts the day of week.
 
 
CLOCK  DATE   MODE                        
 08/28/2009          Fr  10:01A 
Function: Allows the user to switch to European date format (2009/08/28) from US format (08/28/2009).
 
 
CLOCK  YEAR                        
 08/28/2009          Fr  10:01A 
Function: Adjusts the year setting.
 
 
CLOCK  MONTH                        
 08/28/2009          Fr  10:01A 
Function: Adjusts the month setting.
 
 
CLOCK  DATE                        
 08/28/2009          Fr  10:01A 
The clock is set.
 
Table 19 
– Clock Setting Screens 
NOTE: The clock does not automatically adjust for Daylight Savings Time, and requires manual adjustment. 
E. PROGRAMMING THE SYSTEM SETTING 
System Setting Program Access 
NOTE
: Programming the boiler control is not possible when the boiler is firing. Make sure any input which can create a demand on the 
boiler, such as the tank thermostat, is turned off, so the boiler will remain idle to allow programming.  
 
SCREEN 
DESCRIPTION 
ENTER   MENU   CODE 
000 
To access the boiler setting program, press and hold the ENTER Key for 4 seconds, until the display shows the screen 
at left.
 
 
ENTER   MENU   CODE 
925 
Using the arrow keys on the display, log in your 
System Menu Access Code “925”. To confirm code, press ENTER 
to access system setting program navigation menu.
 
Table 20 
– System Setting Access 
F. SYSTEM SETTING PROGRAM NAVIGATION 
Once the System Menu Access Code is confirmed, the user can begin to set the system setting menu. Use the   arrow keys on 
the display to navigate through the system setting program. To change a setting, press ENTER. System settings can be increased by 
pressing the UP ARROW and decreased by pressing the DOWN ARROW on the display. When done, press ENTER. Setting will stop 
blinking and you can move on to next setting. Press RESET to exit programming and store settings. Listed below are the boiler settings 
that can be programmed into the control.