.  8 single-ended 4-20 mA input channels 
.  Non-incendive field circuits 
.  HART pass-through 
.  HART variable and status reporting 
.  2- or 4-wire transmitters  
.  open and short circuit detection 
.  24 V dc bussed field power required 
Module Specifications
Inputs 
Number of channels ...............................................8, single-ended 
Nominal signal range (span) ..........................................4 to 20 mA 
Full signal range.................................................................1 to 23 mA
Line fault detection 
     Short circuit current .....................................................> 23.5 mA
     Open circuit current ......................................................<  0.5 mA
Output voltage (@ 20mA).............................................13.5 V (min.)
Output current ..............................................................32 mA (max.)
Accuracy (over temp range) ...................................± 0.1% of span
Resolution ..................................................................................16 bits
Repeatability ................................................................0.05% of span
Isolation
     (any channel to Railbus) .................................................100 V ac
     (between channels)................................................................none
NT
-8101-HI-TX
Image Description
8 Channel Analog Input
4–20 mA with HART® 
Configurable Parameters
Input filter time constant .................................user defined value
Input dead zone .................................................user defined value
Drive on failsafe............................. disabled /upscale /downscale
Channel status.......................................................... active /inactive
HART variable and status reporting ................... enable /disable
Response Time
Signal change to availability on Railbus 
     4–20 mA mode .........................................................27 ms (max.)
     HART mode......................................................0.75 s per channel
Safety
FM non-incendive field wiring parameters (each channel) 
V
oc
 = 28.7 V; I
sc
 = 33 mA; C
a
 = 0.17 µF; L
a
 = 11.0 mH
Power Supplies
Railbus (12V) current .....................100 mA (typ.), 150 mA (max.)
Bussed Field Power 2-wire Tx...................................300 mA (max.) 
(@ 24 V dc ±10%) 4-wire Tx.........................................60 mA (max.)
Mechanical
Module Key Code .............................................................................A1 
Module width ............................................................................42 mm 
Weight............................................................................................200 g 
Field Terminals (2-WIRE TX) 
Field Wiring
Recommended 
Field Terminal
Compatible 
Field Terminal
General Purpose
NT-8602-FT-ST
Standard
NT-8604-FT-FU 
Fused
Class 1, Div 2 
or Zone 2 hazard-
ous area
NT-8601-FT-NI 
Non-incendive 
NT-8603-FT-FU
Non-incendive 
 
Field Terminals (4-WIRE TX) 
Field Wiring
Recommended 
Field Terminal
Compatible 
Field Terminal
General Purpose
NT-8615-FT-4W
-
Class 1, Div 2 
or Zone 2 hazard-
ous area
NT-8615-FT-4W 
-
NovaTech 8000 Series I/O Family
Copyright © 2007 NovaTech, LLC. All rights reserved. All trademarks 
are properties of their respective owners. NovaTech is a registered 
trademark  of  NovaTech,  LLC.  The  information  in  this  literature  is 
subject to change without notice and is not to be construed as a 
warranty.  DS_8101_0607