3 Operating the SAMMS-MV Device
The communications inputs must be included in the ladder logic
(control circuit).
3.6 Ladder Diagrams
3.6.1 Library of Standard Ladder Diagrams
The SAMMS-MV library of more than 40 ladder diagrams
the standard control circuits and the input and output assign-
ments for the library. You can use the library with the following
starter types:
across-the-line, non-reversing
across-the-line, reversing
two-speed, two winding
two-speed, one-winding, constant or variable torque
two-speed, one-winding, constant horsepower
reduced-voltage, autotransformer
reduced-voltage, reactor
For each starter type, the library includes seven control types:
local two-wire
local three-wire
local three-wire, remote two-wire
local two-wire, remote two-wire
local three-wire, remote three-wire
remote two-wire
remote three-wire
SAMMS-MVE has seven preloaded circuits (ladder diagrams)
for use with across-the-line (FVNR) applications. SAMMS-MVX
may be used with any of the circuits.
For details on the library of standard ladder diagrams, refer to
the SAMMS Standard Circuit Manual.
3.6.2 Custom Ladder Diagrams
For special motor control applications not covered by the library
of standard ladders, you can construct custom ladder dia-
grams using the input and output devices and their associated
symbols for the SAMMS-MV device. Siemens personnel can
build these custom ladder diagrams or you can build your own.
You can purchase an optional IBM PC-compatible software
package to develop custom ladder diagrams for special control
applications. The package also includes a library of standard
symbols. The package enables you to reconfigure existing
SAMMS-MV devices to meet changing plant needs. Refer to
the Custom Software Manual for the SAMMS device, Bulletin
CP 3291.
Figure 3.2 Ladder symbols used with the SAMMS-MV device (sheet 1)