Fitting XI/ON base modules
The XI/ON base modules are fitted on the right of the XC600 
controller on the mounting rail:
X
Fit the groove of the XI/ON base module onto the mounting rail 
from underneath  .
X
Tilt the upper end back and press the base module against the 
mounting rail until you can hear it snap into position
 
.
X
Push the base module as far left as possible until the two snap 
hooks on the side of the adapter or neighbouring base module 
click into position  . 
X
Fix the XI/ON modules using the end bracket and end plate on 
the mounting rail.
X
Once you have fitted all modules, switch on the 24 V power 
supply on the XC-POW50-XION-UPS module in order to provide 
the 5 V supply to the XI/ON modules.
X
Check that the modules are working correctly (no fitting errors, 
no gaps).
Engineering
Control cabinet design
The arrangement of components in the control cabinet is an impor-
tant factor in ensuring that system and machine functions are free 
of interference. During the planning and design stages, as well as 
during implementation, it must be ensured that the power and 
control sections are separated. The power section includes the 
following components:
• Contactors
• Coupling modules
• Transformers 
• Frequency inverters
• Current converters
Dividing the control cabinet into to areas with different power and 
interference levels is recommended as an effective prevention 
against electromagnetic interference. In small control cabinets, 
this can often be provided sufficiently by using separators in order 
to reduce interference.
h
Further information on mounting and wiring is provided in 
the XI/ON manuals, e.g. ”Hardware and Engineering” – 
XI/ON PROFIBUS-DP (AWB2700-1394).
1
2
3
Figure 6:
Fitting XI/ON modules
2
3
1
h
Wire the base modules after they have been fitted and 
before you have fitted the electronic modules!
h
Only apply the field voltage on the XC600 controller base 