Moeller Marine XControl PLC System AWB2700-1428GB User Manual

Page of 54
Hardware and Engineering
12/01 AWB2700-1428GB
10
Wiring example (overview)
Switching the power supply on/off
The UPS ensures that the XC600 controller is switched off properly 
in the event of a power supply failure. This requires the inputs/
outputs of the UPS device and the other devices to be wired as 
shown below.
If the supply voltage to the UPS device drops, the controller is 
supplied with the battery supply voltage. The contact ”C1” in the 
UPS device opens and the circuit at the Power Fail input of the 
power supply module is interrupted. This will cause the controller 
to initiate the PFI signal, which will cause the system to shut down. 
The controller requires approximately two minutes to do this.
By connecting the Battery off input of the UPS to contact C2, the 
UPS device can switch off the battery supply voltage after two 
minutes. The battery is then used only for these two minutes so 
that  further battery backup protection is ensured  occur. If power 
is restored after two minutes, the controller will start up again 
according to how the operating mode selector switch is set.
A different routine is followed if the power supply to the UPS 
returns within two minutes: while the power to the UPS device has 
failed, the controller is at first initially supplied by the battery 
voltage until power is restored. As the UPS device signals the 
power failure to the controller (Power Fail input), the controller 
starts a system shutdown (2 minutes). The following message will 
be shown on the display: ”PFI shut down in progress”.The opera-
tion ends with the message ”TURN OFF YOUR CONTROLLER” on 
the display.
In this case, the controller has not detected a power failure. When 
the PLC is restarted, the power supply of the UPS system must be 
switched off and on again. If the start is to take place automati-
cally, an on-delayed timer must be used to lengthen the interrup-
tion to more than 2.5 minutes (
Fig. 10).
In the event of a power failure the PLC will then shut down after 
two minutes and will restart automatically after 2.5 minutes.
Figure 8:
Example of wiring
Non-grounded control circuits must be provided with  insulation 
monitoring.
L1
V
24 
V
6
5
N
PE
a
L1
L2
L3
N
PE
c
d
e
b
1
2
+24 V
0 V
~
f
c
XC600
XC-POW50-
UPS-XION
V
0
24 
V
0
XC-ADP-XION
XI/ON-Modul
C
1
24 
V
1
V
1
Figure 9:
Wiring between UPS device and the XC600 power 
supply module
XC600 (XC-POW50-(XION-)UPS)
UPS device
1
Batt.
off
0 V
0 V
0
24 V 
H
24 V
0
1
2
Power
Fail
Power
Supply
Power
Supply
3
0 V
L1
N
PE
2
4
5
C1
C2
6 7
8
9 10 11 12
b
a
Battery
2 min.
UPS
Release