Hardware and Engineering
12/01 AWB2700-1428GB
14
X
Assign the memory range beginning with start address CE000 
to the first module (CANopen or PROFIBUS-DP) to be 
configured.
The input/output devices assigned to this module are connected to 
the module bus system via address CE000.
X
Assign the range starting with address CC000 to the second 
module and D4000 to the third.
Bus terminating resistors
Bus terminating resistors must be provided at both ends of the 
cable.
XC-NET-CAN CANopen module 
General
The module provides the ISO 11898 interface between the CPU 
module and the CANopen bus. 
Task of the module
The module provides the master function for CANopen bus. It 
organises and operates the data exchange between the user 
program and the connected slaves. Up to 126 nodes can be 
connected to a line.
The CANopen modules can be fitted between the power supply 
module and the CPU module. Up to three modules (PROFIBUS-DP 
or CANopen) can be fitted.
Engineering
CANopen interface
The module can be connected to the CANopen bus via the isolated 
ISO 11898 interface.
Pin assignment
Connector assignment in accordance with the CiA DS 102 
(CAN Physical Layer for Industrial Applications) standard.
Power supply
The power supply module provides the 5 V supply to the modules 
via the PC/104 bus.
Set the system power supply so that the connected remote stations 
on the CANopen line are switched on simultaneously or before the 
controller. This prevents any errors occurring during the starting of 
the CANopen line.
Start/Stop behaviour
Setting the OMS to the STOP position will cause all the outputs of 
the remote devices to be set to 0.
An interruption on the line will cause all inputs of the disconnected 
devices (receive data) to be interpreted by the PLC as 0 signals and 
the outputs set by the PLC in the output module to be reset. 
Devices that are still connected with the PLC will continue to be 
interrogated.
Configuring the module address
Up to three XC-NET-DP-M (PROFIBUS-DP) or XC-NET-CAN 
(CANopen) modules can be used in any combination. Reserve a 
memory range for each module in the CPU by defining a module 
address for each one:
X
Set the address for each module using the jumpers in the 
jumper field from range 13 to 17 (
following figures).
Figure 20:
Example configuration with three modules and the 
assigned addresses
h
When using the ZB4-209-DS2  PROFIBUS plug, the bus 
terminating resistor can be enabled or disabled via the 
slide switch on the plug.
Figure 21:
CANopen interface
Figure 22:
Pin assignment of the CANopen interface
SUB-D plug 
connector
Signal
Meaning
2
CAN_L
CAN_L bus cable
3
CAN_GND
CAN reference potential
7
CAN_H
CAN_H bus cable
3
4
1
2
5
8
9
6
7