Hardware and Engineering
12/01 AWB2700-1428GB
12
Expansion with XI/ON modules
The following XI/ON base modules can be connected directly to 
the XC-ADP-XION base module:
• Modules with tension clamp connection
• Modules with screw connections without C rail
Bus refreshing modules and power feeding modules cannot be 
connected directly.
XC-POW50-UPS/XC-POW50-XION-UPS power supply 
modules
General
A base module and a power supply module form one unit. The 
following table shows the combination possibilities of both 
modules. The only difference between the modules is their expan-
sion capability with XI/ON modules.
Task
The modules convert the 24 V DC power supply to +5 V DC, 
+12 V DC and –12 V DC (for XC-POW50-XION-UPS) supplies, and 
provide the voltages for the function modules via the PC/104+ 
bus. The XC-POW50-XION-UPS power supply module also 
provides a 5 V DC supply to XI/ON modules via the XI/ON module 
bus.
As the XC600 controller is PC-based, it must be ensured that the 
program is closed and the operating system shut down properly 
before the device is switched off. The supply of the power supply 
module must therefore be backed up by means of an uninterrupt-
ible power supply (UPS). If the supply voltage drops, the UPS sends 
a Power Fail signal to the PLC which then initiates a shutdown of 
the system. The UPS unit will then keep the output voltage 
constant for at least two minutes in order to ensure the trouble-
free completion of the shutdown.
Setup
The module contains a board with the PC/104+ bus. Another 
board provides the interface for the XI/ON modules and connects 
the power supply module with the base module. 
Engineering 
XC-NET-DP-M PROFIBUS-DP module
General
The module provides the interface between the CPU module and 
the PROFIBUS-DP bus that is compliant with industrial standard 
EN 50170 Vol. 2.
Task
The module provides the master function for PROFIBUS-DP. It 
organises and operates the data exchange between the user 
program and the connected slaves. Up to 31 slaves can be 
connected to one line. Several sections can be connected together 
using repeaters, enabling up to 125 slaves to be connected. 
Base module
Power supply module
Expansion
XC-ADP
XC-POW50-UPS
XI/ON
XC-ADP-XION
XC-POW50-XION-UPS
Figure 13:
Block diagram of the power supply module
Figure 14:
Connections of the XC-POW50-UPS/
XC-POW50-XION-UPS
Power Fail connection
24 V DC connection
Plug-in terminals, connection cross-sections:
– flexible with ferrule 0.5 mm
2
 to 2.5 mm
2
– solid 0.5 mm
2
 to 2.5 mm
2
Power
Fail
24 V 
H
XC-POW50-XION-UPS
XC- ADP-XION
24 V 
H
–12 V
+12 V
5 V
USV
Diagnostics
XI/ON
Module-
bus
Fieldbus-
supply
24 V 
H
XI/0N
ISA Interface
ISA-BUS
Power
Fail
Power F
ail
Power
Supply
1
2
24Vo 0Vo
c
c
a
b