Rack-mount precautions 
Familiarize yourself with the following precautions before rack-mounting the 
appliance: 
Anchoring the equipment rack—The equipment rack must be anchored to an 
unmovable support to prevent it from falling over when one or more devices is 
extended in front of it on slide assemblies. The anchors must be able to 
withstand a force of up to 113 kg (250 lbs.). You must also consider the weight of 
any other device installed in the rack. 
Main AC power disconnect—You're responsible for installing an AC power 
disconnect for the entire rack unit. This main disconnect must be readily 
accessible, and it must be labeled as controlling power to the entire unit, not just 
to the appliances. 
Grounding the rack installation—To avoid the potential for electrical shock, 
you must include a third wire safety grounding conductor with the rack 
installation. If the appliance power cords are plugged into AC outlets that are part 
of the rack, then you must provide proper grounding for the rack itself. If the 
appliance power cords are plugged into wall AC outlets, the safety grounding 
conductor in each power cord provides proper grounding only for the appliance. 
You must provide additional grounding for the rack and other devices installed in 
it.