Vinotemp VINOSONOMA250 Manual
11
6) Access and Modification of the Frequent Parameters (F TYPE)
1) Press the button 6 for more than 5 seconds (in case of alarm, first silence the
buzzer) until the display displays PS.
2) Press button 5 or button 7 to show the parameter whose value has to be
changed; press to display the associated value.
3) Press button 5 or button 7 to change the value.
4) Press button 6 to temporarily confirm the new value and go back to display the
parameter code. In order to modify the other parameters, start back from point 3.
7) Storage of the new values
Press button 6 at least for 5 seconds to store the new value and exit the
“PARAMETERS MODIFICATION” procedure. For timing parameters only: switch
off and switch on the controller in order to make them immediately effective
without waiting for the following cycle.
8) To exit without modifying any parameter
Do not press any button for at least 60 seconds (TIME OUT).
3. Normal Sounds
1) Press the button 6 for more than 5 seconds (in case of alarm, first silence the
buzzer) until the display displays PS.
2) Press button 5 or button 7 to show the parameter whose value has to be
changed; press to display the associated value.
3) Press button 5 or button 7 to change the value.
4) Press button 6 to temporarily confirm the new value and go back to display the
parameter code. In order to modify the other parameters, start back from point 3.
7) Storage of the new values
Press button 6 at least for 5 seconds to store the new value and exit the
“PARAMETERS MODIFICATION” procedure. For timing parameters only: switch
off and switch on the controller in order to make them immediately effective
without waiting for the following cycle.
8) To exit without modifying any parameter
Do not press any button for at least 60 seconds (TIME OUT).
3. Normal Sounds
1) The rattling, gurgling sounds are normal when the compressor is running.
2) The click sound is normal when the compressor starts and stops.