Thermador VTR1330P Installation Instruction

Page of 19
English 2
Installation
Step 1: EXHAUST-AIR MODE
Equipment Needed
Equipment Included
Exhaust air should not be directed into a smoke or exhaust 
flue that is currently used for other purposes, nor into a 
shaft that is used for ventilating rooms in which stoves or 
fireplaces are also located.
Exhaust air must be discharged in accordance with official 
and statutory regulations only (e.g. national building 
regulations).
Local regulations must be observed when discharging air 
into smoke or exhaust flues that are not otherwise in use.
When the extractor hood is operated in exhaust-air mode 
simultaneously with a different burner which also makes 
use of the same chimney (such as gas, oil or coal-fired 
heaters, continuous-flow heaters, hot-water boilers), care 
must be taken to ensure that there is an adequate supply of 
fresh air, which will be needed by the burner for 
combustion.
Safe operation is possible provided that the under-pressure 
in the room where the burner is installed does not exceed 4 
Pa (0.04 mbar).
This can be achieved if combustion air can flow through 
non-lockable openings, e.g. in doors, windows and via the 
air-intake/exhaust-air wall box or by other technical 
measures, such as reciprocal interlocking, etc.
If the air intake is inadequate, there is a risk of carbon 
monoxide poisoning from combustion gases which are 
drawn back into the room.
An air-intake/exhaust-air wall box by itself is no guarantee 
that the limiting value will not be exceeded.
NOTE: When assessing the overall requirement, the 
combined ventilation system for the entire household must 
be taken into consideration. This rule does not apply to the 
use of cooking appliances, such as ranges and ovens.
Step 2: PREPARING THE 
WALL
䙚  The wall must be flat and perpendicular.
䙚  Ensure that the wall is capable of providing a firm hold 
for mounting screws and anchors.
Weight: 15.4 kg / 39 lbs
Technical Information
Electrical Requirements: 120 V; 60 Hz, max. 5.7 A 
Duct Size: 6" (152 mm)
䙚  Drill and Bit
䙚    Screwdriver
䙚    Rubber Mallet
䙚   Anchors (4)
䙚    Screws (4)
䙚    Connector
IMPORTANT SAFETY INSTRUCTIONS
Attach the inner wall blower inside the building only, 
but not in living rooms.
When attaching the inner wall blower, ensure that it 
is accessible for maintenance and repairs.
The plug-and-socket connections of the electric 
cables must be located inside the building, 
according to local code.
DO NOT reduce the 10" (254 mm) diameter of the 
pipes connected to the extractor hood except when 
used with downdraft systems.
DO NOT install the blower
outdoors.
in an environment with dripping water.
near flammable materials.
in rooms which may contain gas or other fuels.