TROUBLESHOOTING 
GENERAL TROUBLESHOOTING 
SYMPTOM
POSSIBLE CAUSE
ACTION
1.  Glass Soots
A. Flame impingement on logs
A. Install log set per the instructions  
  Inspect the injector and air intake area. Make sure this area does 
not have any blockage from debris and clean.  
  Check gas supply.
2.  Flame burn 
blue and lifts 
off burner 
(ghosting)
A. Insufficient oxygen being supplied
A. Ensure that the vent cap is installed properly and free of debris. 
Ensure that the vent system joints are tight and have no leaks.  
Ensure that no debris has been blocking the inner air intake at the 
bottom back of the combustion chamber.  Ensure that the glass is 
properly secure and latch.
GLASS REPLACEMENT 
AND
 BLOWER 
•  Never operate fireplace if glass is broken.
•  Replace any glass that is chipped, cracked, or broken. Replacement glass assemblies MUST be supplied by fireplace 
manufacturer — No substitute materials may be use.
Always  use  gloves  when  handling 
broken glass. 
CAUTION 
Make  sure  the  glass  panel  edges 
do  not  touch  any  metal  parts  during 
thermal expansion. 
W
ARNING
OPTIONAL BLOWER ACCESSORY - BLOT
WIRING DIAGRAM FOR BLOWER