AEG 8000012364 BAL User Manual

Page of 42
"UniVert 2" inverter 
 
Page 33 of 42 
8000012364 BAL, en 
Mechanical stability 
and vibration resistance................. To VDE 0160 Version 5.88 
Item 7.2.2 
Surface painted with ...................... RAL 7032 (front panel) 
Dimensions (w x h x d) .................. 483 x 174 x 460 mm 
(19" x 4 height modules) 
(type 1.5 and 3.3 kVA) 
483 x 174 x 400 mm 
(19" x 4 height modules) 
(type 2.5 kVA) 
Weight ........................................... Approx. 46.5 kg (type 3.3 kVA) 
Approx. 39 kg (type 2.5 kVA) 
Approx. 33.1 kg (type 1.5 kVA) 
Noise generation ........................... < 50 dB(A) 
Connections 
X1 DC input: .................................. Screw terminal 10 ... 25 mm² 
(type 1.5 and 3.3 kVA) 
Screw terminal 0.5 ... 10 mm²  
(type 2.5 kVA) 
X2 AC output: ................................ Screw terminal 0.5 ... 10 mm² 
X3 remote signals: ......................... Screw terminal 0.2 ... 2.5 mm
2
 
PE conductor: ................................ M4 thread 
CAN bus interface X6 .................... 10-pin socket connector with 
insulation displacement 
technology 
in acc. with DIN 41651 
CAN bus interface X7 .................... 16-pin socket connector with 
insulation displacement 
technology 
in acc. with DIN 41651 
8.2 
General Data SBS 
Required AC fuse .......................... Max. gL 125 A  
Manufacturing and type test .......... In acc. with DIN 60146 Part 1-1 
Emitted interference in acc. with EN 50081-1 
- Conducted interference  .............. In acc. with EN 55022 Class "B" 
- Emission ...................................... In acc. with EN 55022 Class "B" 
Noise immunity in acc. with EN 50082-2 
- Housing ....................................... ESD test to EN 61000-4-2, 
6 kV contact 
HF field to EN 61000-4-3, 
10 V/m (30 MHz – 1 GHz)