AEG 8000012364 BAL User Manual

Page of 42
"UniVert 2" inverter 
 
Page 35 of 42 
8000012364 BAL, en 
Protection class ............................. IP 20 
Cooling .......................................... Forced air cooling 
Intake air temperature ................... At rated current 0°C to 45°C, 
measured below the SBS  
Storage temperature...................... -20°C to +70°C 
Ambient conditions ........................ IEC 721 Part 3-3 Class 3K3 / 3Z1 / 
3B1 / 3C2 / 3S2 / 3M3 
Site altitude .................................... Up to 2000 m above sea level 
Mechanical stability 
and vibration resistance................. In acc. with VDE 0160 
Version 5.88 Item 7.2.2 
Surface painted with ...................... RAL 7032 (front panel) 
Dimensions (W x H x D) ................ 483 x 174 x 400 mm 
(19" x 4 height modules) 
Weight ........................................... Approx. 13.5 kg 
Noise generation ........................... < 50 dB(A) 
Connection system 
X1 AC mains input: ........................ Screw terminal 10 ... 25 mm
2
 
X2 AC output: ................................ Screw terminal 10 ... 25 mm
2
 
X4 remote signals: ......................... Screw terminal 0.2 ... 2.5 mm
2
 
PE conductor: ................................ M4 thread 
X6 CAN bus interface .................... 10-pin socket connector with 
insulation displacement 
connection system 
in acc. with DIN 41651 
X7 CAN bus interface .................... 16-pin socket connector with 
insulation displacement 
connection system 
in acc. with DIN 41651