AEG 8000012364 BAL User Manual

Page of 42
"UniVert 2" inverter 
 
Page 36 of 42 
8000012364 BAL, en 
8.3 Electrical 
Data 
 
Type 
E-number 
G48 – 60 E230/14,4/2rfg-CFp3,3 
3000000352 
G220 E 230/14,4/2rfg-CFp3,3 
300000601  
Rated output capacity 
3.3 kVA
 
with power factor 
0.8
 
Power factor range 
0 inductive to 0 capacitive
 
Rated output voltage 
230 V 
±0.5 static, ±3% dynamic at 100% load connection
 
Output frequency 
50 Hz 
±0.05%
 
THD factor 
< 3%
 
Rated output current 
14.4 A 
14.4 A
 
DC rated input voltage 
48 V -15% / 60 V +20% 
220 V -15% +20%
 
DC rated current 
64 A at 48 V / 51 A at 60 V 
14 A at 220 V
 
Efficiency 
> 85% 
> 86% 
DC input current ripple 
< 10% of DC rated current
 
Monitoring systems 
 
DC undervoltage, switch-off 
Fault < 85% of 48 V (40.8 V), 
without delay 
Acknowledgement > 103% of 48 V 
(49.4 V), 15 s delay 
Fault < 85% of 220 V (187 V), 
without delay 
Acknowledgement > 103% of 
220 V (226 V), 15 s delay
 
DC overvoltage, switch-off 
Fault > 128% of 60 V (76.8 V), 
without delay 
Acknowledgement < 125% of 60 V 
(75 V), 15 s delay 
Fault > 128% of 220 V (281 V), 
without delay 
Acknowledgement < 125% of 
220 V (275 V), 15 s delay
 
AC undervoltage, switch-off 
Fault < 90% rated (207 V), 2.5 s delay 
Acknowledgement by ON/OFF switch
 
Overtemperature, switch-off 
Fault > 80 
°C, acknowledgement < 70 °C, approx. 5 s delay