8.3 Electrical
Data
Type
E-number
G48 – 60 E230/14,4/2rfg-CFp3,3
3000000352
G220 E 230/14,4/2rfg-CFp3,3
300000601
Rated output capacity
3.3 kVA
with power factor
0.8
Power factor range
0 inductive to 0 capacitive
Rated output voltage
230 V
±0.5 static, ±3% dynamic at 100% load connection
Output frequency
50 Hz
±0.05%
THD factor
< 3%
Rated output current
14.4 A
14.4 A
DC rated input voltage
48 V -15% / 60 V +20%
220 V -15% +20%
DC rated current
64 A at 48 V / 51 A at 60 V
14 A at 220 V
Efficiency
> 85%
> 86%
DC input current ripple
< 10% of DC rated current
Monitoring systems
DC undervoltage, switch-off
Fault < 85% of 48 V (40.8 V),
without delay
Acknowledgement > 103% of 48 V
(49.4 V), 15 s delay
Fault < 85% of 220 V (187 V),
without delay
Acknowledgement > 103% of
220 V (226 V), 15 s delay
DC overvoltage, switch-off
Fault > 128% of 60 V (76.8 V),
without delay
Acknowledgement < 125% of 60 V
(75 V), 15 s delay
Fault > 128% of 220 V (281 V),
without delay
Acknowledgement < 125% of
220 V (275 V), 15 s delay
AC undervoltage, switch-off
Fault < 90% rated (207 V), 2.5 s delay
Acknowledgement by ON/OFF switch
Overtemperature, switch-off
Fault > 80
°C, acknowledgement < 70 °C, approx. 5 s delay