Hearth & Home Technologies be-36-c User Manual

Page of 65
Hearth & Home Technologies   •  BE-36-C, BE-36-CIPI  •  397-981 Rev. V  1/07
22
Combustible Wall Penetration
Frame a hole in a combustible wall for an interior wall 
shield fi restop, (Figure 6.2) whenever a wall is penetrated. 
Use same size framing materials as those used in the wall 
construction. The wall shield fi restop maintains minimum 
clearances and prevents cold air infi ltration.
Non-Combustible Wall Penetration
If the hole being penetrated is surrounded by noncombus-
tible materials such as concrete, a hole with diameter one 
inch greater than the pipe is acceptable.
B.  Wall Penetration Framing
Figure 6.3  Exterior Wall Hole
*  Shows center of vent framing hole for top or rear venting. 
The center of the hole is one (1) inch (25.4 mm) above the 
center of the horizontal vent pipe.
WALL
HEAT
SHIELD
HEAT
SHIELD
3 in. TOP
CLEARANCE
WALL
SHIELD
FIRESTOP
1 in. CLEARANCE
BOTTOM & SIDES
7 in.
A
B
C
D
*
*
A.  Pipe Clearances to Combustibles
Vent  Clearances and Framing
6
Fire Risk.
Explosion Risk.
Maintain vent clearance to combustibles as 
specifi ed.
•  Do not pack air space with insulation or other 
materials.
Failure to keep insulation or other materials 
away from vent pipe may cause fi re.
Figure 6.1  Pipe Clearances
1 in. CLEARANCE
AROUND VERTICAL
SECTIONS
3 in. TOP
CLEARANCE
1 in. SIDE AND
BOTTOM CLEARANCE
NOTE: Slope 
not required.
WARNING
Figure 6.2  Horizontal Venting Clearances to Combustible Materials
A
B
C
D
BE-36-C
in.
36 1/2
24 3/8
35 1/2
23 3/8
mm
927
619
902
594
Note: Heat shields MUST overlap by a minimum of 1-1/2 in. (38 mm).
The heat shield is designed to be used on a wall 4 in. to 7-1/4 in. (102 
mm to 184 mm) thick
. If wall thickness is less than 4 in. (102 mm) the 
existing heat shields must be fi eld trimmed. If wall thickness is greater than 
7-1/4 in. (184 mm) a DVP-HSM-B will be required.