D.   Installing Roof Flashing and
       Vertical Termination Cap
To install roof fl ashing see Figure 8.16.  
For installation of vertical termination cap see minimum vent 
heights for various pitched roofs (see Figure 8.16) . 
Caulk the gap between the roof fl ashing and the outside 
diameter of the pipe.  Also caulk the perimeter of fl ashing 
that contacts roof surface as shown in Figure 8.18.
To attach the vertical termination cap, slide the inner col-
lar of the cap into the inner fl ue of the pipe section  and 
place the outer collar of the cap over the outer fl ue of the 
pipe section.
Secure with three screws into the outer fl ue. Secure the cap 
by driving the three self-tapping screws (supplied) through 
the pilot holes in the outer collar of the cap into the outer 
fl ue of the pipe (see Figure 8.17).
Roof Pitch                            H (Min.) Ft.
Flat to 6/12.......................................1.0*
Over 6/12 to 7/12 ...........................1.25*
Over 7/12 to 8/12 .............................1.5*
Over 8/12 to 9/12 .............................2.0*
Over 9/12 to 10/12 ............................ 2.5
Over 10/12 to 11/12 ........................ 3.25
Over 11/12 to 12/12 .......................... 4.0
Over 12/12 to 14/12 .......................... 5.0
Over 14/12 to 16/12 .......................... 6.0
Over 16/12 to 18/12 .......................... 7.0
Over 18/12 to 20/12 .......................... 7.5
Over 20/12 to 21/12 .......................... 8.0
Figure 8.16     Minimum Height from Roof to 
                        Lowest Discharge Opening
* 3 foot minimum in snow regions
HORIZONTAL
OVERHANG
VERTICAL
WALL
GAS DIRECT VENT 
TERMINATION CAP
12
X
ROOF PITCH
IS  X/ 12
LOWEST
DISCHARGE
OPENING
2 FT.
MIN.
20 INCHES MIN.
H (MIN.) - MINIMUM HEIGHT FROM ROOF
TO LOWEST DISCHARGE OPENING
Figure  8.17   
SCREWS
CAULK
STORM 
COLLAR
(1 of 3)
TERMINATION  CAP
Fire Risk.
Explosion Risk.
Inspect external vent cap regularly.
•  Ensure no debris blocks cap.
•  Combustible materials blocking cap may 
ignite.
• Restricted air fl ow affects burner operation.
WARNING
CAULK
Figure  8.18   