Hearth & Home Technologies be-36-c User Manual

Page of 65
35
Hearth & Home Technologies   •  BE-36-C, BE-36-CIPI  •  397-981 Rev. V  1/07
NOTE: Have the gas supply line installed in accordance 
with local building codes, if any. If not, follow ANSI 
223.1. Installation should be done by a qualifi ed  installer 
approved and/or licensed as required by the locality. (In 
the Commonwealth of Massachusetts installation must be 
performed by a licensed plumber or gas fi tter.) 
A.  Fuel Conversions
Before making gas connections ensure that appliance be-
ing installed is compatible with the available gas type.
Any natural or propane gas conversions necessary to 
meet the appliance and locality needs must be made by 
a qualifi ed technician using Hearth & Home Technologies 
specifi ed and approved parts.
Fire Risk.
Explosion Hazard.
High pressure will damage valve.
•  Disconnect gas supply piping BEFORE 
pressure testing gas line at test pressures 
above 1/2 psig.
•  Close the manual shutoff valve BEFORE 
pressure testing gas line at test pressures 
equal to or less than 1/2 psig.
B.  Gas Pressures
Proper input pressures are required for optimum appli-
ance performance. Gas line sizing requirements need to 
be made following NFPA51.
C.  Gas Connection
Verify inlet pressures.
•  High pressure may cause overfi re condition.
•  Low pressure may cause explosion.
•  Verify minimum pressures when other 
household gas appliances are operating.
Install regulator upstream of valve if line pressure 
is greater than 1/2 psig.
Gas Information
9
NOTE:  Gas line may be run from either side of the appliance 
provided the hole in the outer wrap does NOT exceed 2-1/2 
inches in diameter and does not penetrate the fi rebox.
NOTE:  A listed (and Commonwealth of Massachusetts 
approved) 1/2 inch (13 mm) T-handle manual shut-off valve 
and fl exible gas connector are connected to the 1/2 inch (13 
mm) control valve inlet. 
•  If substituting for these components, please consult 
local codes for compliance.
Pressure requirements for appliance are shown in the 
table below. Minimum pressures must be met when other 
household gas appliances are operating.
Refer to Reference Section 16 for location of gas line 
access in appliance.
Gas Leak Risk
•  Support control when attaching pipe to prevent 
bending gas line. 
NOTE: The gap between supply piping and gas access 
hole may be caulked with high temperature caulk or stuffed 
with non-combustible, unfaced insulation to prevent cold air 
infi ltration.
Pressure
Natural Gas
Propane
Minimum
Inlet Pressure
5.0 inches
w.c.
11.0 inches
w.c.
Maximum Inlet
Gas Pressure
14.0 inches
w.c.
14.0 inches
w.c.
Manifold
Pressure
3.5 inches
w.c.
10.0 inches
w.c.
WARNING
WARNING
WARNING