Start-Up Operation
Multiple Systems With Multiple
Evaporators (Requires A Smart
Controller)
 
•  Check all wiring connections to be sure
 
 
they are correct and tight. 
 
•  On the condensing units 
 
 
Check setting of time delay relay.  
 
 
 
It should be set at 1 minute  
 
 
 
(the second marker). 
 
 
Check the low pressure switch  
 
 
 
setting on freezer units. It must be set 
 
 
 
to 0 psig cut-out, 10 psig cut-in to  
 
 
 
allow positive start and operation, 
 
 
 
especially in cold ambient. This  
 
 
 
can be changed to a higher value in  
 
 
 
warmer climates. On cooler units,  
 
 
 
the low pressure switch has a fixed  
 
 
 
setting and cannot be adjusted. 
 
•  Turn power on. 
S
S
S
M
CU
S
S
S
M
CU
S
S
S
M
CU
M
S
S
S
CU
SMART
CONTROLLER
SYSTEM 1
SYSTEM 2
SYSTEM 3
SYSTEM 4
M = Master Evaporator 
S = Slave Evaporator 
CU = Condensing Unit
MULTIPLE SYSTEM CONNECTION
(See Smart Controller instruction manual for more details)
 
•  On the MASTER evaporator 
 
 
DO NOT REMOVE the room sensor 
 
 
 
from any evaporator 
 
•  On the SLAVE evaporators. All Beacon II  
 
 
boards are shipped with the factory  
 
 
default as a “MASTER” evaporator. 
 -  Each SLAVE evaporator must be 
 
 
 
changed to identify it as a SLAVE.  
 
 
 
Use the “
PROGRAM REVIEW” 
 
 
 
button to scroll until 
“SLA” appears,
 
 
 
then use the “
SELECT” knob to 
 
 
 
select 
“YES” then press “ENTER.”
 
•  Use the Beacon II Smart Controller to  
 
 
set system parameters.  See Beacon  
 
 
II Smart Controller installation  
 
 
instructions for more details.