Start-Up Operation
Single System With 1 Evaporator
 
•  Check all wiring connections to be sure
 
 
they are correct and tight. 
 
•  On the condensing unit 
 
 
Check the setting of time delay  
 
 
 
relay. It should be set at 1 minute  
 
 
 
(the second marker). 
 
 
Check the low pressure switch  
 
 
 
setting on freezer units. It must be  
 
 
 
set to 0 psig cut-out, 10 psig cut-in  
 
 
 
to allow positive start and operation, 
 
 
 
especially in cold ambients. This  
 
 
 
can be changed to a higher value in  
 
 
 
warmer climates. On cooler units, the 
 
 
 
low pressure switch has a fixed 
 
 
 
setting and cannot be adjusted. 
 
•  Turn power on 
 
Start-Up Operation
 
•  On the evaporator 
 
 
Use the “
PROGRAM REVIEW” 
 
 
 
button to scroll through settings. 
 
 
Check “
rEF” (Refrigerant Type). 
 
 
 
Factory defaults are: Air Defrost  
 
 
 
R-22, Electric Defrost R-404A.  
 
 
 
Change to the refrigerant being used. 
 
 
Check 
“bot” (Box Temperature). 
 
 
 
Factory defaults are: air defrost  
 
 
 
35°F and electric defrost –10°F.  
 
 
 
Change to the desired temperature. 
 
 
Review and change other setting if  
 
 
 
necessary 
 
 
See procedures below on how to  
 
 
 
change settings.