DR4300 Circular Chart Recorder Product Manual 
12/03 
Procedure 
The procedure for calibrating the current proportional output is listed in Table 5-11. Make sure “LOCK” in 
the Set Up group is set to “NONE.”    
For display recorders with 2 pens, be sure the correct input is on display—INP 1 or INP 2 indicator is lit. 
 Press 
FUNC
  key to change input on display to agree with the control loop output to be calibrated. 
 
Table 5-11  Procedure for Calibrating Current Output  
Step Description 
Press 
Action/Result 
Enter Calibration Mode 
SET 
 UP
 
until you see 
  CAL
Upper Display
 
   CURENT
Lower Display
 
If “CAL” doesn’t appear or prompt access is denied, check 
the “LOCK” configuration. 
Calibrate 0 % 
FUNC
 
You will see: 
Upper Display
a value (approximately 365) 
     ZERO
Lower Display
 
 
 
 
or 
 
Until the desired 0 % output is read on the milliammeter. 
Use the values shown below depending on the action of 
your recorder. 
Calibrate 100 % 
FUNC
 
Stores the 0 % value and, you will see: 
Upper Display
a value (approximately 1800) 
     SPAN
Lower Display
 
 
 
 
or 
 
Until the desired 100 % output is read on the milliammeter. 
Use the values shown below depending on the action of 
your recorder.